MOULDLKnowledge BaseElectrical Knowledge Base3D Model DownloadsMembership
中文版Model Store »
Knowledge Base › Electrical Knowledge Base › Button marking and colour code for multi-point control
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Button marking and colour code for multi-point control

National standards state exactly what each button colour means, yet sites still paint e-stops green or starts red. This note sets out the colour, marking and mounting rules so installation passes acceptance and never misleads the operator.

1. How it works

Per GB/T 4026 and GB/T 5226.1, red means stop, e-stop and off; green means start and on; yellow means caution and intermittent motion; blue means forced or indicative action. The e-stop must be a red mushroom head latching button, never another colour. Start green, stop red is the law; a red flat button instead of a mushroom, or a green maintenance button, both mislead.

2. Practice and pitfalls

Colour alone is not enough; each button needs a text or graphic label such as start, stop, e-stop, or the IEC symbol. Labels must be permanent, clear and not hidden by oil. Identical buttons get numbers. Prefer GB/T 4728 graphic symbols for international alignment. Mount boxes at 0.6 to 1.7 metres with the e-stop within reach; use IP54 or better outdoors and stainless in corrosive sites.

3. Button colour code

ColourMeaningUseBan
RedStop e-stop offMushroomNot start
GreenStart onStart btnNot e-stop
YellowCautionInchingNot red
BlueForcedResetSparing
LabelText symbolGB/T 4728Clear
Place0.6-1.7 mReachableNo block

4. Notes

Button colours are a safety language: red stop, green start, yellow caution, blue forced, with e-stop always red mushroom latching. Keep text and symbol together, facing the operator, with proper rating. Check all four at acceptance.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Button colour and marking per GB/T 4026 and GB/T 4728, IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① E-stop green flat: misleads
② Colour only no text: confused
③ Label oily: unclear

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL