National standards state exactly what each button colour means, yet sites still paint e-stops green or starts red. This note sets out the colour, marking and mounting rules so installation passes acceptance and never misleads the operator.
Per GB/T 4026 and GB/T 5226.1, red means stop, e-stop and off; green means start and on; yellow means caution and intermittent motion; blue means forced or indicative action. The e-stop must be a red mushroom head latching button, never another colour. Start green, stop red is the law; a red flat button instead of a mushroom, or a green maintenance button, both mislead.
Colour alone is not enough; each button needs a text or graphic label such as start, stop, e-stop, or the IEC symbol. Labels must be permanent, clear and not hidden by oil. Identical buttons get numbers. Prefer GB/T 4728 graphic symbols for international alignment. Mount boxes at 0.6 to 1.7 metres with the e-stop within reach; use IP54 or better outdoors and stainless in corrosive sites.
| Colour | Meaning | Use | Ban |
|---|---|---|---|
| Red | Stop e-stop off | Mushroom | Not start |
| Green | Start on | Start btn | Not e-stop |
| Yellow | Caution | Inching | Not red |
| Blue | Forced | Reset | Sparing |
| Label | Text symbol | GB/T 4728 | Clear |
| Place | 0.6-1.7 m | Reachable | No block |
Button colours are a safety language: red stop, green start, yellow caution, blue forced, with e-stop always red mushroom latching. Keep text and symbol together, facing the operator, with proper rating. Check all four at acceptance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Button colour and marking per GB/T 4026 and GB/T 4728, IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.