A control circuit is logic made of contacts: series is AND, parallel is OR, normally closed is NOT. This page covers how to express and simplify control logic, translating process requirements into contact networks.
Contact networks have three basic operations. Series is AND: everything must close, such as a start button in series with a thermal relay NC contact. Parallel is OR: any branch closes the path, such as two start buttons for two-station control. A normally closed contact is NOT: it opens when energised, which is why stop buttons are wired NC in series. Hold-in adds memory: a contactor auxiliary contact parallels the start button and keeps the coil alive after release. With these three operations any relay circuit decomposes into a logic expression.
Write the process conditions as logic before drawing: permissive to start equals guard closed AND no fault AND selector in auto, which draws as three contacts in series. Simplify by merging contacts, sharing busbars and placing interlocks close to their coils. Intermediate relays are the workhorse of simplification: drive one KA from a multi-condition combination, then let its contacts feed downstream, cutting contact count and clutter. Always re-verify after simplifying so no path bypasses an interlock.
Keep the expression readable: order series conditions top-down with safety first, so e-stop and guard chains sit at the head of every coil; annotate each contact with its source tag; mark time logic with the delay direction, delayed closing or delayed opening. Pair complex logic with a truth table or sequence table so the drawing states its intent instead of leaving readers to guess line by line.
| Relation | Contact form | Typical use | Note |
|---|---|---|---|
| AND | Contacts in series | All start conditions met | Safety conditions first |
| OR | Contacts in parallel | Two-station starting | Branches independent |
| NOT | Normally closed contact | Stop and interlock | NC in series is safest |
| Hold-in | Parallel aux contact | Contactor keeping | Paired with NC stop |
| Delay | KT timed contact | Star-delta changeover | Mark delay direction |
| Mutual lock | Opposite NC in series | Reversing contactors | Always in pairs |
Logic expression is the craft of translating process language into drawings: write the logic before drawing and design stays on track; read contacts back into logic during troubleshooting and the fault clears faster. Truth and sequence tables are the user manual of logic drawings, worth attaching to every complex circuit.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contact logic drafting per GB/T 6988.1; graphic symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.