Two contactors must never close at the same time, otherwise the supply phases short directly. This article explains how a NC auxiliary contact of one contactor is wired in series with the other coil so the two cannot be energized together, plus the standard wiring and verification steps.
An interlock places the normally closed auxiliary contact of KM1 in series with the coil circuit of KM2, and vice versa. When KM1 is energized its NC contact opens and forcibly breaks KM2 coil path, so KM2 cannot pull in. This guarantees at most one contactor is active at any moment, preventing phase-to-phase short circuits and mechanical collisions. Always confirm on the schematic that the interlock uses NC contacts, typically labelled 13 to 14 or 21 to 22; using NO contacts instead makes the interlock useless.
During wiring, first insert KM1 NC contact into KM2 coil branch and KM2 NC contact into KM1 coil branch. Use twin push buttons so pressing forward first breaks the reverse branch then makes forward. Keep coil control voltages identical, usually AC 220 V or 380 V, and size the control transformer at 1.5 times the total holding power. After wiring, verify every series contact with a continuity buzzer before applying load.
| Item | Correct wiring | Wrong outcome |
|---|---|---|
| Interlock contact | Use NC contact | NO contact fails |
| Series position | In opposite coil branch | Parallel does nothing |
| Control voltage | Coils same voltage | Dropout on high load |
| Push button | Twin button preferred | No button interlock |
| Verification | Test simultaneous close | Short risk unseen |
Interlocks are the basic protection against supply short circuits and mechanical crash in forward-reverse, dual-supply and standby circuits. Always perform the simultaneous-button test after wiring to prove the two contactors cannot close together.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear per GB 14048.4 and GB 14048.5, machinery safety per GB/T 5226.1, referencing IEC 60947 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.