Extending a latch loop with an intermediate relay

When the latch contacts run out, or signals must go to several places, or the button is far, add an intermediate relay KA. This page shows how to extend the latch.

1. How it works

A contactor has few auxiliary contacts (2 to 4 NO and NC each); when the latch must also drive lamps, alarms, PLC inputs and a second machine, they run out. The intermediate relay KA has many contacts, low coil power and small size, ideal to amplify and convert signals. Use KA NO contacts in place of or parallel to the latch point to get several synchronized run-state signals.

2. Practice and pitfalls

Wire the parallel of start and KM aux to drive the KA coil (or let the KM aux drive KA directly); when KA pulls, its NO contacts feed: self-hold (one KA NO back across the start), a run lamp, a PLC input X, and a second contactor. KA rating (5 to 10 A) is control only, never the main loop, and its coil voltage matches the control supply.

3. KA extension

UseWireNote
HoldKA NO parsync
Lampcontactstate
PLCcontact Xisol
Multicontactrating
RemoteSB driveel1117
Pitmain loopweld

4. Notes

When contacts run out, let the KM aux drive a KA coil and use its NO contacts for self-hold, lamp, PLC input and other machines. KA is control-only, voltage matched, labels clear, and synchronized with KM. For long button runs KA saves voltage drop.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control relay GB/T 14048 with IEC 60947; PLC GB/T 15969. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① KA on main: weld
② Wrong coil V: burn
③ No labels: messy

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.