Overload relay placement in forward-reverse circuits

With one overload relay in a reversing circuit, the wrong position halves the protection. This article compares placement options: before versus after the reversal, one shared unit versus one per direction, and the wiring points for thermal elements and auxiliary contacts, so overload protection covers both directions.

1. How it works

Put the thermal relay after the two contactors merge and before the motor: whichever direction runs, current passes the same thermal elements and both directions stay protected. Wiring it only in the forward branch leaves reverse unprotected; placing it on the supply side of the contactors fails the same way. Drawing reviewers should treat this point as a mandatory check.

2. Practice and pitfalls

The normal practice is one shared three-pole relay for both directions, set to the motor rated current, simple and reliable. Two relays fit only when the two directions carry very different loads, such as hoisting versus lowering; wiring gets complex and each setting needs verification. The shared scheme has a bonus: with the NC contact in the common control path before the branch point, an overload in either direction cuts the whole control supply and stops both. All three thermal elements must sit in the three phases; omit one and phase-loss protection degrades. Set the trip current between 0.95 and 1.05 times nameplate, prove it with an overload test, and choose manual reset so a hot motor never restarts into an unfixed overload.

3. Overload relay placement options

OptionWiringEffect
After reversal, sharedBefore the motorBoth directions (recommended)
Forward branch onlyOne directionReverse unprotected
On supply sideBefore contactorsWrong, ineffective
Two relaysOne per directionOnly for uneven loads
NC in common pathBefore branch pointOverload cuts both

4. Notes

Placement rule: after the merge, before the motor, all three elements in circuit, NC in the common path. Review drawings here first; a wrong spot voids everything. Set the trip, prove it with a test, and keep manual reset so the protection holds in both directions.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 for apparatus and thermal relays, GB/T 5226.1 for machinery safety, IEC 60947-4 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Relay in one direction only: the other runs unprotected
② One thermal element omitted: phase-loss protection degrades
③ Automatic reset chosen: restart into overload burns the motor

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.