VFD and soft starter symbols and how to mark them

Variable frequency drives and soft starters are both motor control devices with distinct symbols. This page explains the standard drawing of each and the annotations that keep their roles clear on the drawing.

1. How it works

A variable frequency drive is a rectangular box with a waveform or VFD mark inside, letter U or the word drive. It rectifies and inverts the supply to deliver adjustable frequency and voltage, so the symbol stresses its energy conversion role; some drawings add an arrow meaning variable frequency. Annotate rated power such as 11kW, input 380V, output 0 to 50Hz and the control mode. Main power lands on the box sides and control wiring lands on its terminal row.

2. Practice and pitfalls

A soft starter is a rectangular box with a ramp or rising arrow showing voltage rising from low to full, letter U or the label soft start. It is a thyristor voltage regulator: once starting finishes a bypass contactor KM closes and the motor runs at full voltage. So the drawing shows the soft start box plus the bypass contactor, annotated with starting current multiple such as 3 times and starting time such as 15 seconds. The essential difference from a drive: the soft starter only shapes the start, it cannot control speed, so never draw one where the other is meant.

3. VFD and soft starter symbol table

DeviceSymbol featureLetter codeMarking points
Variable frequency drivebox plus waveformU/VFDpower, frequency range
Soft starterbox plus rampUstart time and current
Bypass contactorcontactsKMcloses after start
Brake unitbox plus resistorUbrake resistor marked
ReactorcoilLreactance marked

4. Notes

A waveform box means a drive and a ramp box means a soft starter; the two functions differ and must not be swapped. A soft starter always needs its bypass contactor drawn, parameters and frequency range belong beside the symbol, and control terminals must not be omitted or commissioning cannot find the interfaces.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive and soft start symbols per GB/T 4728.7; adjustable speed systems per GB/T 12668 and IEC 61800 series. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Soft starter drawn as a drive: the process needs speed control and the purchased device cannot provide it
② Bypass contactor omitted on the soft starter: motor loses a phase once starting finishes
③ Drive control terminals not drawn: commissioning cannot find the start-stop and analogue interfaces

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »