Variable frequency drives and soft starters are both motor control devices with distinct symbols. This page explains the standard drawing of each and the annotations that keep their roles clear on the drawing.
A variable frequency drive is a rectangular box with a waveform or VFD mark inside, letter U or the word drive. It rectifies and inverts the supply to deliver adjustable frequency and voltage, so the symbol stresses its energy conversion role; some drawings add an arrow meaning variable frequency. Annotate rated power such as 11kW, input 380V, output 0 to 50Hz and the control mode. Main power lands on the box sides and control wiring lands on its terminal row.
A soft starter is a rectangular box with a ramp or rising arrow showing voltage rising from low to full, letter U or the label soft start. It is a thyristor voltage regulator: once starting finishes a bypass contactor KM closes and the motor runs at full voltage. So the drawing shows the soft start box plus the bypass contactor, annotated with starting current multiple such as 3 times and starting time such as 15 seconds. The essential difference from a drive: the soft starter only shapes the start, it cannot control speed, so never draw one where the other is meant.
| Device | Symbol feature | Letter code | Marking points |
|---|---|---|---|
| Variable frequency drive | box plus waveform | U/VFD | power, frequency range |
| Soft starter | box plus ramp | U | start time and current |
| Bypass contactor | contacts | KM | closes after start |
| Brake unit | box plus resistor | U | brake resistor marked |
| Reactor | coil | L | reactance marked |
A waveform box means a drive and a ramp box means a soft starter; the two functions differ and must not be swapped. A soft starter always needs its bypass contactor drawn, parameters and frequency range belong beside the symbol, and control terminals must not be omitted or commissioning cannot find the interfaces.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drive and soft start symbols per GB/T 4728.7; adjustable speed systems per GB/T 12668 and IEC 61800 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.