Wrong dimensions on a layout mean a cabinet that will not take the devices. This page covers how to dimension device outlines and mounting clearances, and how to tie cutouts to device sizes.
Express device sizes in three ways: draw true-to-sample outlines at scale with width, depth and height; use one simplified outline per class with a size label, such as a 45mm wide contactor; or draw mounting bands for grouped devices with total width and divisions. The rule is accurate footprints: body width plus cooling gap decides rail layout, verified from datasheets, never from memory. Depth needs wiring room: device depth plus bending space of at least 80mm.
Usable clearance numbers: 20 to 30mm between adjacent contactors and breakers for cooling; arc-blowout space above breakers of 50mm or the datasheet arc zone; creepage and clearance between terminals of different voltage systems, at least 25mm plus barriers between 380V and 24V; handling space of 30mm between pushbuttons and an unobstructed 40mm zone around e-stops; and 30mm between devices and the inside of the door for service access.
Tie cutouts to device sizes: drill panel holes per the datasheet with the upper tolerance, a 22mm button in a 22.2 to 22.4mm hole; mark hole positions by coordinates from one datum with plus or minus 0.2mm tolerance; and keep cutouts linked to internal positions so a shifted hole does not strand the wiring. Check the finished annotation with a sample assembly, and prove-fit one cabinet before a batch run.
| Item | Content | Reference values | Note |
|---|---|---|---|
| Outline | Width, depth, height | Contactor 45mm wide | Verified from datasheet |
| Row spacing | Cooling gap | 20 to 30mm | Wider for hot devices |
| Arc clearance | Above breakers | 50mm and up | Per datasheet arc zone |
| Voltage separation | Terminals of mixed systems | 25mm minimum | Add barriers |
| Handling space | Between pushbuttons | 30mm and up | E-stop unobstructed |
| Cutout tolerance | Hole and pitch | Upper +0.2mm | Prove-fit first |
Dimensions and clearances are the technical core of a layout; complete, sourced numbers let fabrication and assembly land first time. Keep a plant quick card of common outlines and gaps at the drafting desk, and both speed and accuracy rise while rework drops.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Clearance and creepage per GB/T 5226.1 and GB/T 14048.1; layout drafting per GB/T 6988.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.