Equipment always gains wires later; with no spare range, new wires get jammed in and create duplicates. Here is how to reserve numbers up front.
After commissioning, wires are almost always added: new sensors, changed loops, expanded stations. If numbers are packed with no headroom, new wires are inserted mid-range or started elsewhere, breaking the sequence, duplicating and conflicting with old logic. A reserved range is a blank pool kept in each zone so additions land in the pool without disturbing the original series and stay easy to find later.
Reserve about 10%~20% per function zone. Example: power 101~119 in use, 120~129 spare; control 201~219 in use, 220~229 spare. Keep spares at the tail or as a separate block, labelled spare and not casually used. For large growth open the next whole block (130~149). In the ledger list spares separately; on change take from spares first, and only open a new block and revise the drawing when spares run out.
| Zone | In use | Spare |
|---|---|---|
| Power | 101~119 | 120~129 |
| Control | 201~219 | 220~229 |
| Signal | 301~319 | 320~329 |
| Ratio | Keep 10-20% | Never full |
| Use | Log it | Revise |
| Big growth | New block | e.g. 130-149 |
Rule: reserve 10-20% per zone, spares at the tail or a separate block, labelled and not casually used. Additions land in the pool without breaking the series, uses are logged and revised, large growth opens a new block. Manage spares as a separate ledger column.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988 series, graphical symbols per GB/T 4728, item codes per GB/T 5094. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.