Switching off is not enough for maintenance: the control circuit may still be live and capacitors hold charge. This page walks the isolation procedure for main and control circuits, from switching points to lockout-tagout and stored energy.
Follow five steps in order. Switch off: open the main breaker and release the stored-energy mechanism, and with control tapped downstream the control circuit dies too. Test: use a tester matched to the voltage level on main incoming terminals and on control terminal blocks, and for drive-fed machines wait five minutes or more for the DC bus to discharge. Discharge large capacitor loads to earth and confirm. Lock: fit a personal padlock on the operating handle. Tag: hang the do-not-operate notice. All five steps, in that order, no exceptions.
Modern machines have more than one feed: main supply, control supply, PLC 24V, heater circuits, maintenance sockets and UPS bypasses can all be live points. Before isolation, audit the drawings and build one power-point list per machine, open each feed and verify. Mark hidden sources in red, such as a second incoming feeder, fire-interlock re-energisation and capacitor storage units. Any supply not on the list must be traced on drawings first; never assume there is only one feed.
Restoration has its own discipline: count people and tools, remove earths and temporary links, remove tags and personal locks (only your own), check insulation and wiring restoration, then close and test-run. The person in charge issues the energisation order, and multi-crew jobs end only when every permit is closed. After re-energising, exercise the control loops unloaded before loading the machine. Log the whole sequence on the work permit and file it for a closed loop.
| Step | Action | Tools | Pass criterion |
|---|---|---|---|
| Switch off | Open main switch, release energy | Operating handle | Open position, mechanically locked |
| Test | Test mains and control separately | Voltage-matched tester | No voltage confirmed |
| Discharge | Earth capacitive loads | Discharge rod, gloves | Bus below 36V |
| Lock | Personal lock on handle | One lock one key | Cannot be closed |
| Tag | Hang do-not-operate notice | Standard sign | Visible and complete |
| Restore | Count, untag, unlock, test | Permit process | Double-signed closure |
Safe isolation rests on trustworthy break points and a verifiable dead state; drawings must show the opening point of every feed. Train with accident cases about hidden supplies until checking every source becomes reflex; one lucky gamble can be fatal.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Isolation procedures per GB/T 5226.1 (IEC 60204-1) and electric safety work rules GB 26860. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.