When the motor runs only sometimes while the button is held, the pushbutton contact is the prime suspect from oxidation or weak spring. This page shows how to confirm it fast and trace which contact is at fault.
Typical signs: the motor starts and stops while you hold, needs repeated presses, or the contactor chatters a beat after release. After ruling out supply and coil issues, focus on the NO jog button SB. Dust, damp and oxidized silver build resistance; weak spring or sluggish return also cause on-off flicker.
Steps: with power off, measure the button with an ohmmeter, it should read near 0 ohm pressed and infinite released, tens of ohm means bad contact; temporarily short the button terminals, if jog then works the button is the fault; open it, clean blackened contacts with fine paper or replace; check terminal tightness; if it still flickers after replacement, look at other coil-loop joints. Use the right meter range to avoid burning it.
| Step | Action | Judge |
|---|---|---|
| Observe | on-off flicker | suspect SB |
| Ohmmeter | resistance | pressed ~0 |
| Bypass | short SB | ok means SB bad |
| Open | oxidized | clean |
| Wires | loose term | tighten |
| Upgrade | IP65 box | dust wet |
For button flicker suspect the jog contact first: measure off-power, bypass to confirm, clean the oxide. In damp dusty sites use a higher-protection button and replace by rated life. Do not treat a button fault as a contactor fault, and never short live to spark.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Pushbuttons fall under GB/T 14048 with IEC 60947; site wiring GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.