Loop numbers are the street addresses of a drawing: follow U1 V1 W1 or 101 and you can walk the wiring. This page explains numbering rules for main and control circuits so any point on the sheet can be located at a glance.
Number the main circuit by phase and device: supply lines L1 L2 L3, after the breaker U1 V1 W1, after contactor KM1 U2 V2 W2, ending at motor terminals U V W; multiple identical motors take prefixes such as 1U 1V 1W and 2U 2V 2W. DC circuits mark positive with odd numbers or a plus sign and negative with even numbers or minus. The principle is stepwise: every element crossed advances the terminal number, so wiring can be walked end to end by numbers alone, and break points carry identical numbers on both sides.
Control loops use zone numbering: supply loops 1 to 99, control from 101 in functional blocks such as 101 to 119 for start-stop, 121 to 139 for interlocks, 141 to 159 for timing and counting, and 201 upward for signalling. Odd numbers conventionally sit on the positive side and even on the negative or neutral side, though some companies use continuous numbering. Every wire number is unique, printed on both sides of terminal blocks, and grid references such as C4 let readers jump straight to a component.
Back the rules with two tables: a wire list recording number, start, end, size and colour, and a terminal list recording both wire numbers on every terminal. Change drawings before changing wires, and log recycled numbers to prevent duplicates. On site, trace by number: put the meter across two numbered terminals and follow the numbers, and even a ten-year-old cabinet untangles in half an hour. For legacy cabinets, renumber during major overhauls and refit wire markers once, benefiting the whole service life.
| Circuit | Rule | Example | Point |
|---|---|---|---|
| Main phases | L1 L2 L3 in, U1 V1 W1 out | U2 V2 W2 after KM1 | Advance past each device |
| Multiple motors | Serial prefix on letters | 1U, 2U | No duplicates in one set |
| DC polarity | Odd positive, even negative | 101/102 | Polarity explicit |
| Control supply | Zone 1 to 99 | L, 1, 2 | Kept apart from loops |
| Start-stop loops | 101 to 119 | 101/102 | Odd live, even return |
| Signalling loops | From 201 | 201/202 | Blocked by function |
Numbering is the addressing system of the drawing set; publish one rule and enforce it plant-wide, stating the version where legacy schemes differ. Manage spares and wire markers from the wire list, and when numbers disagree, stop and verify rather than guess.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Identification of terminals and markings per GB/T 4026 and GB/T 4728; terminal marking per IEC 60445. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.