Mixing main and control circuits in star-delta is a major taboo: interference, hard tracing, unsafe. This article covers separation principles, duct division, grounding and shielding, and how to map terminal numbers after separation.
The main circuit carries large current (tens to hundreds of amps) with arcs and strong fields; the control circuit is small signal (220 V, milliamps). Mixed wiring lets main-circuit EMI couple into control, causing KT mis-action and contactor chatter, also raising shock risk. Separation isolates faults, speeds tracing and is safer, the standard practice, never mix for convenience.
In the cabinet route main circuit in the left or lower duct, control in the right or upper, with a partition between. Terminal blocks split into a high-current zone (thick wire, big terminals) and a thin-wire control zone with clear marking. Use matching wire-number prefixes per device (KM1 main contacts 1/2/3, coil 11/12/13) to avoid mistakes.
Ground the main enclosure and motor frame reliably; if control cable runs long parallel to main, use shielded wire with the shield grounded at one end only. After separation, verify wire by wire per number before power: control from L1L2, main phase sequence correct. Redraw and archive the wiring diagram after any change.
| Item | Main | Control | Key |
|---|---|---|---|
| Duct | left/lower | right/upper | partition |
| Terminals | high-current | thin zone | zones |
| Wire no | 1/2/3 | 11/12/13 | prefix |
| EMI | strong field | small sig | isolate |
| Ground | frame motor | shield one-end | solid |
| Check | by number | same source | archive |
Rule: main left-lower, control right-upper, partition between, matching wire prefixes, shield one-end grounded. Separation is not fussiness but a hard rule against interference and shock, and it speeds tracing.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring per IEC 60204-1, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.