Double interlock means button interlock plus contactor interlock, the safest standard form of a forward-reverse circuit. This article dissects the circuit layer by layer: main-circuit crossing, break-before-make at the buttons and contact-level NC interlock, showing where every wire lands so you can wire it from the drawing.
The circuit carries three protective layers. First, the composite buttons are mechanically linked: pressing forward first opens the NC contact wired in the reverse branch, then closes the forward NO. Second, contactor interlock puts KM1 NC in the KM2 coil branch and KM2 NC in the KM1 coil branch. Third, the stop button NC and the overload relay NC sit in the common supply path. Together, a stuck button, a welded contact or an overload can never energize both coils at once.
Wiring layer by layer. Main circuit: supply feeds both KM1 and KM2 main contacts through QF and FU, KM2 load side crosses two phases and parallels with KM1 onto FR, whose output goes to the motor. Control circuit: stop button SB1 NC in the common path; the forward branch takes SB2 NO in series with the KM1 coil and a KM1 NO across SB2 for latching; the reverse branch mirrors this. Interlock wires: KM1 NC into the reverse branch, KM2 NC into the forward branch, and the composite-button NC contacts crossed into the opposite branches for button-level interlock. On pressing SB2 the reverse branch opens first, then KM1 picks up and latches; pressing SB3 opens the forward branch, KM1 drops, its NC resets, and KM2 then pulls in. At no instant are both coil paths alive.
| Operation | Acts first | Acts next | Layer |
|---|---|---|---|
| Press forward SB2 | Open reverse NC | KM1 latches | Button interlock |
| Press reverse SB3 | Open forward NC | KM2 latches | Button interlock |
| KM1 engaged | KM1 NC opens | Reverse branch locked | Contactor interlock |
| Overload occurs | FR NC opens | Both branches cut | Thermal protection |
| Press stop SB1 | Common path opens | All released | Total protection |
The key is wiring every interlock line: two button NCs and two contactor NCs, none may be skipped. Verify layer by layer with a no-load test: single press, both press, release for latch. Any layer that fails must be fixed before startup.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 and GB 14048.5 for apparatus, GB/T 5226.1 for machinery safety, IEC 60947-5-1 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.