When the supply sags the latch drops and the machine stops or misbehaves. This page covers the voltage tolerance a latch loop needs and the fixes.
A contactor has pick-up and drop-out thresholds: generally pick-up at 85 percent of rated voltage and drop-out at 70 percent or below. It works reliably between 85 and 110 percent; below pick-up it will not pull in, above drop-out it stays in. The latch loop holds by the coil, so when voltage falls under the drop-out the KM releases, the latch opens and the motor stops, which is both a weakness and under-voltage protection.
A short sag from inrush, lightning or surge can drop the latch and stop a continuous process; jitter near the threshold makes the contactor chatter and wear; long low voltage leaves it weakly pulled and buzzing; high voltage over-current heats the coil. Keep control supply quality with a regulator or isolating transformer on important loads.
| Param | Threshold | Effect |
|---|---|---|
| Pick-up | >=85% | no pull |
| Drop | <=70% | releases |
| Reliable | 85-110 | works |
| Sag | <70 | false stop |
| Low | weak | buzz |
| High | over | heat |
The latch needs control voltage 85 to 110 percent of rated; below drop-out it stops, which is under-voltage protection. Use an independent regulated supply, wide-voltage coil, an intermediate relay for long wires, and under-voltage release on critical machines. Measure actual control voltage within tolerance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor GB/T 14048.4 with IEC 60947-4-1; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.