Cascaded stopping: when any upstream motor stops, downstream must follow

In sequential control, whenever an upstream motor stops — by button, overload or trip — every downstream motor must stop with it, or material piles up mid-line. The trick is a single cascade contact; this page shows the wiring and the on-site checks.

1. How it works

The KM1 auxiliary NO does double duty: it seals KM1 and licenses the KM2 branch. While KM1 runs, KM2 may run; the moment KM1 drops — overload, E-stop or power loss — that series NO opens and KM2 de-energizes. No extra hardware is needed; one contact enforces both start order and stop order.

2. Numbers and practice

Separate normal stop from protective stop. Each motor keeps its own thermal NC in its own coil circuit, so FR1 dropping KM1 pulls the cascade open behind it. The line-wide stop button sits at the head of the common bus and kills everything at once. If the process wants a drain-out delay, replace the cascade NO with a KT off-delay contact, typically 3 to 10 s adjustable.

3. Pitfalls and fixes

Verify three ways: force-release KM1 with an insulated tool and watch KM2 stop instantly; trip FR1 with its test button and check the shutdown order; press the E-stop and confirm every contactor drops and nothing restarts on reset — a fresh start press is required.

4. Upstream stop events and downstream response

Stop causeUpstream stateDownstream response
Front stop buttonKM1 releasedKM2 and beyond stop at once or delayed
Front thermal tripFR1 cuts KM1cascade opens, rear motors drop in order
Front phase lossbreaker trips, KM1 offwhole line stops by cascade
E-stop pressedall circuits deadevery contactor releases
Momentary outageseal contacts openno auto restart, new start press needed

5. Notes

Agree the stopping timing with the process engineer before wiring: conveyors usually stop at once to prevent pile-up, loaded belts may want a drain delay, then record it in the commissioning sheet.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Stop functions per GB/T 5226.1 / IEC 60204-1 stop categories. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Using a front NC instead of NO: logic reversed, rear starts only after front stops, always run the cascade check
② E-stop wired below a coil branch: only one motor stops, the E-stop must interrupt the common bus first
③ Wrong timer contact for delayed stop: a delay-on contact lets material accumulate, use an off-delay contact

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.