Root-cause analysis of wiring errors that prevent stopping

The most dangerous thing in multi-point control is finishing the wiring and finding no stop button can stop the machine. This note analyses the root causes of this no-stop error and how to catch it before energising, eliminating the safety hazard.

1. How it works

Cause one: a NC stop mistaken as NO, or the start and stop swapped, leaves a permanent open in the stop chain so the motor will not even start. The real can-start-cannot-stop case is a stop of wrong type wired NO with a jumper, or the holding contact bypassing the stop chain. In every case the chain should open on press but stays closed.

2. Practice and pitfalls

Cause two: the KM holding contact is wrongly placed across the front of the stop chain to the coil, spanning the whole chain. Once latched, even all stops pressed keep the circuit alive through the hold. This is very hidden, looks normal, and only drawing review and point-by-point metering reveal it. Always verify the hold crosses only the start before energising.

3. No-stop cause table

RootSymptomPre-power test
Stop NONo start/no stopPress should open, reads closed
Hold bypassStart not stopHold only across start
Stop jumperedPress still onCheck button ends
E-stop outE-stop voidConfirm in chain
Wrong typeReversedCheck NO/NC
Drawing diffHiddenCompare point

4. Notes

No-stop is a safety risk and must be blocked by de-energised testing before commissioning. All stops and e-stops series in the main chain, the hold strictly across the start, press every button off-power and meter, then sign off.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: E-stop and stop safety in GB/T 5226.1 chapter 9; IEC 60204-1 e-stop requirement. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Holding contact spanning the stop chain gives start but never stop, hidden by normal looks
② Jumper across the stop button ends keeps it closed when pressed, no stop at all
③ An e-stop not in the main chain is a dummy that cannot cut power in an emergency

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.