How to set up multi-speed operation on a VFD

Multi-speed lets a motor run several fixed speeds without a PLC, using input terminals as a binary code. This page covers wiring, parameter setup and priority.

1. How it works

Multi-speed uses多功能 inputs such as X1, X2, X3 as binary bits, giving 000 to 111 or up to 8 speed steps, each frequency written into a parameter like Pr.4 to Pr.12. The drive reads the terminal levels and outputs the matching frequency. It beats analog speed control on noise immunity and costs less than fieldbus, ideal for conveyors and fans that only need a few fixed speeds.

2. Practice and pitfalls

First assign X1~X3 to multi-speed select 1/2/3, then write each step frequency into Pr.4 to Pr.12, e.g. Pr.4=15 Hz, Pr.5=25 Hz, Pr.6=40 Hz. Set run command to external terminals and give multi-speed priority over analog. Save to EEPROM or power-cycle, or settings are lost. Multi-speed overrides analog by default but yields to the keypad unless priority is changed.

3. Terminal coding and frequency table

X3X2X1 stateSpeed stepExample freq
000Step 0 stop/base0 Hz or base
001Step 1Pr.4=15 Hz
010Step 2Pr.5=25 Hz
011Step 3Pr.6=40 Hz
100Step 4Pr.7=50 Hz
111Step 7Pr.10=10 Hz

4. Notes

Set terminal function codes first, then write step frequencies, then confirm source and save. Eight steps cover most fixed jobs; verify each step on the monitor. Always pull up floating terminals to avoid false codes.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Adjustable-speed drives per GB/T 12668.2; control circuits per GB/T 14048.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Floating terminals without pull-up cause false speed steps; add pull-up resistors
② Unclear analog vs multi-speed priority makes frequency fight; multi-speed wins by default
③ Upper limit set too low clamps the step; raise the limit to see it take effect

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.