Multi-speed lets a motor run several fixed speeds without a PLC, using input terminals as a binary code. This page covers wiring, parameter setup and priority.
Multi-speed uses多功能 inputs such as X1, X2, X3 as binary bits, giving 000 to 111 or up to 8 speed steps, each frequency written into a parameter like Pr.4 to Pr.12. The drive reads the terminal levels and outputs the matching frequency. It beats analog speed control on noise immunity and costs less than fieldbus, ideal for conveyors and fans that only need a few fixed speeds.
First assign X1~X3 to multi-speed select 1/2/3, then write each step frequency into Pr.4 to Pr.12, e.g. Pr.4=15 Hz, Pr.5=25 Hz, Pr.6=40 Hz. Set run command to external terminals and give multi-speed priority over analog. Save to EEPROM or power-cycle, or settings are lost. Multi-speed overrides analog by default but yields to the keypad unless priority is changed.
| X3X2X1 state | Speed step | Example freq |
|---|---|---|
| 000 | Step 0 stop/base | 0 Hz or base |
| 001 | Step 1 | Pr.4=15 Hz |
| 010 | Step 2 | Pr.5=25 Hz |
| 011 | Step 3 | Pr.6=40 Hz |
| 100 | Step 4 | Pr.7=50 Hz |
| 111 | Step 7 | Pr.10=10 Hz |
Set terminal function codes first, then write step frequencies, then confirm source and save. Eight steps cover most fixed jobs; verify each step on the monitor. Always pull up floating terminals to avoid false codes.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Adjustable-speed drives per GB/T 12668.2; control circuits per GB/T 14048.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.