A contact resistance in series with the load steals voltage: U×RL/(Rc+RL).
Coils need ~85%Un to pull in reliably; a “half-fed” coil chatters and arcs - worse than a dead one.
Patrol voltage drops segment by segment while live, then confirm with a 4-wire milliohmmeter; replace burned terminals rather than re-tightening.
| Step | Action | Criterion | Tool |
|---|---|---|---|
| 1 | Load voltage | <85%Un = sag | DMM |
| 2 | Source voltage | Rated | DMM |
| 3 | Loop loss | Diff >10% suspicious | Calc |
| 4 | Per-segment drop | Bad segment found | DMM |
| 5 | Contact resistance | Milliohms normal | 4-wire meter |
| 6 | Repair & retest | Back to rated | Full kit |
Apply the points above to Contact resistance and undervoltage at the load, explained by divider action; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 14048.4, GB 14048.5, GB 50171 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.