Chint NB1 versus Delixi CDB6 miniature breakers

Both are mainstream domestic MCBs; specs look alike but details differ. This page puts their parameters side by side for safe choice.

1. How it works

Both are 18 mm modular, 1~63 A, NB1 commonly 6 kA (some 10 kA), CDB6 mostly 6 kA (high-break 10 kA), both to GB/T 14048.2 / IEC 60898. Poles 1P~4P, C/D curves complete, rated 230/400 V, identical trip (C 5~10 In, D 10~20 In). Appearance and 35 mm rail mount are compatible, good interchange.

2. Numbers and practice

Differences are accessories and high-end: NB1 has a fuller accessory ecosystem (auxiliary, alarm, shunt) and wide channels; CDB6 pushes 10 kA high-break and compact sizing. Prices are close, channels differ. Marking clarity, handle feel and wiring capacity (both take ≤25 mm² solid/stranded) are similar. Traps: different brands share the rail but accessories do not interchange; reading brand not breaking capacity, fitting 6 kA at a high-fault point is unsafe; online fakes with inflated specs.

3. Pitfalls and fixes

For general end lighting/socket distribution either works, choose by channel and price; if the point has large prospective fault (near transformer) pick both 10 kA high-break; if rich accessories (remote status, fault alarm) are needed, prefer NB1 ecosystem. Rule: end small current either is fine, key positions watch breaking and accessories. On arrival check breaking marking and 3C certification, avoid uncertified goods.

4. NB1 vs CDB6

ItemChint NB1Delixi CDB6
Modular/A18mm 1~63A18mm 1~63A
Breaking6/10 kA6/10 kA
Curve/poleC/D 1~4PC/D 1~4P
AccessoryFullCompact high
PickChannel/accBreak/compact

5. Notes

Both are 18 mm, 1~63 A, full C/D, to GB/T 14048.2; breaking 6 kA some 10 kA. NB1 has fuller accessories, CDB6 compact high-break. Either for end distribution; pick 10 kA at high-fault points and NB1 for accessories. Verify 3C and avoid fakes.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; MCB per IEC 60898. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Mixed-brand accessories do not interchange
② Reading brand not breaking fits unsafe 6 kA
③ Online uncertified fakes inflate specs

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.