Motors and capacitor banks both show a poor power factor, yet they pull in opposite directions: one absorbs lagging reactive power, the other generates leading reactive power. This page sorts out the phase relationships so overcompensation is never mistaken for inductive behavior again.
In an AC circuit the phase angle between voltage and current decides the character of the load. With an inductive load such as a motor, a transformer or a reactor, the current lags the voltage, the angle is positive and the load absorbs lagging reactive power. With a capacitive load such as a capacitor bank or an overcompensated feeder, the current leads, the angle is negative and reactive power flows back toward the source. The two effects cancel each other, which is exactly why capacitors are used to offset motor magnetizing current.
The numbers behave differently too. A 7.5 kW induction motor sits near 0.2 power factor at no load and climbs to about 0.85 at full load, because its reactive demand falls with slip. A 100 kvar capacitor stage delivers roughly constant reactive power the moment it closes. On site, a clip-on power meter that shows the sign of the phase angle settles the question in seconds: if the display goes leading after a stage switches in, the bank is overcompensated and a step must be removed. Keep the target between 0.9 and 0.95 lagging, because leading operation drives circulating current, adds copper loss in the transformer and lifts the voltage at the end of the feeder.
| Feature | Inductive load | Capacitive load |
|---|---|---|
| Current phase | Lags the voltage | Leads the voltage |
| Reactive direction | Absorbs lagging vars | Delivers leading vars |
| Typical equipment | Motors, transformers, reactors | Capacitors, overcompensated lines |
| Low PF symptom | Large lagging angle | Large leading angle |
| Countermeasure | Switch capacitors in | Switch capacitors out |
Hold power factor between 0.9 and 0.95 lagging and prefer slight undercompensation. Overcompensation creates circulating current that heats the transformer and raises the far end voltage.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power factor and reactive power definitions appear in GB/T 12325, low voltage compensation in GB/T 15576, and power quality assessment follows the IEC 61000-3 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.