Synchronising a synchronous generator: conditions and method

Connecting a generator wrongly means light shock or explosion. This page states the four paralleling conditions, the preparatory synchronising method, and the后果 of wrong connection.

1. How it works

Before paralleling, the incoming machine must match bus voltage within 5 to 10 percent, frequency within 0.1 to 0.2 Hz, phase angle near zero, and phase sequence identical. Any miss causes huge circulating current and impact torque that damages the generator and breaker; sequence is fixed at wiring, the other three are approached in operation.

2. Practice and pitfalls

Preparatory synchronising brings it close then closes: run to rated speed, adjust excitation to match voltage, nudge prime-mover speed slightly high, and watch the synchroscope or lamp method to close at zero phase difference. Automatic units catch the window where voltage, frequency and phase all match. Wrong closing with large frequency or phase difference drives several times rated circulating current and mechanical shock, deforming windings and flashing the breaker; never parallel out of sync and fit out-of-step protection as backup.

3. Synchronising conditions and tolerances for paralleling generators

ConditionRequirementToleranceIf violated
VoltageEqual<10%Circulating current
FrequencyMatched<0.2 HzImpact
PhaseAlignedapprox. 0Torque shock
SequenceIdenticalMust matchReverse rotation
Breaker closeAt zero differenceInstantArc blast

4. Notes

Parallel a generator only when voltage, frequency, phase and phase sequence all agree (within <10%, <0.2 Hz and roughly zero degrees). The synchroniser trims excitation and speed until the synchroscope reads zero or creeps slowly, then close. Wrong synchronisation drives circulating currents of several times rating and torque shocks that deform the windings and blast the breaker; never parallel out of sync and always back it with protection.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Synchronous machines: GB/T 755 / IEC 60034-1; relay protection: GB/T 14285. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Closing with a large phase difference drives several times rated circulating current and blasts the breaker
② Wrong phase sequence spins the machine backwards and wrecks it
③ Without out-of-step protection an accidental wrong paralleling has no backup at all

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.