Unbalanced three phase current burns motors and trips protection, but the root may sit in the supply or the winding. This page gives a measurement order from supply to winding with quantitative thresholds so you can locate the fault by the numbers.
Quantify unbalance as the maximum deviation: unbalance percent equals (max phase current minus average) over average, or commonly (max minus min) over max. Keep running unbalance under 10 percent; above 15 to 20 percent the temperature rise and efficiency loss are clear and the winding will burn if left. Measure at rated load and steady state with a clamp meter on all three phases, since light load exaggerates the apparent deviation and misleads.
About half the cases start in the supply: a 1 percent voltage unbalance drives 6 to 10 percent current unbalance, so first measure bus voltage and if unbalance exceeds 2 percent fix the supply, tightening terminals, replacing pitted contacts or adjusting transformer taps. Single phasing from a blown fuse or open contact sends the other two currents surging with lost torque and heat, and must stop the machine at once or it burns within minutes. Only after clearing the supply test the motor: winding resistance unbalance over 5 percent by bridge points to turn short, open or bad joint; check bearings and broken rotor bars for fluctuating current. The order is voltage, then current, then resistance, then mechanical, and log the three currents against baseline.
| Step | Measure | Criterion or action |
|---|---|---|
| 1 | bus three phase voltage | over 2pct fix supply first |
| 2 | running current | over 10pct needs check |
| 3 | winding resistance | over 5pct turn short or open |
| 4 | check single phase | blown fuse stop at once |
| 5 | bearing rotor | drag or broken bar fluctuates |
Check supply first, since 1 percent voltage unbalance drives 6 to 10 percent current unbalance and over 2 percent means fix the supply; then the motor, where resistance spread over 5 percent signals turn fault and single phasing demands immediate stop. Keep unbalance under 10 percent, measure at rated load, and log against baseline.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Test method per GB/T 1032; rating per GB/T 755 (IEC 60034-1). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.