The 15 kW on the plate is shaft output, not what the meter sees; confusing them ruins wiring and billing. This page clarifies output versus input.
Nameplate rated power Pn is the mechanical power at the shaft (kW), output not input. Input Pin = Pn/η, with η 0.85~0.95. A 15 kW motor at η=0.9 draws about 16.7 kW, the 1.7 kW gap lost as heat. You match load to Pn and size wire to In (derived from input), never mixing them.
People tie billing to input and think the plate kW is the meter reading, but the meter sees Pin; billing on Pn undercounts by 1/η ≈11%. Another confusion: VFD nameplate power is also output driving capability. Traps: billing on Pn undercounts electricity cost; sizing wire on Pn forgets input current is larger and undersizes.
For billing, first get Pin = Pn/η then multiply by hours and price. For wire and breaker use In directly from the plate, the input current. If In is absent, invert In=Pn/(√3·Un·η·cosφ), which is input current. Rule: plate power is shaft output, billing and wiring look at input. Load matches Pn, distribution matches In.
| Concept | Value | Use |
|---|---|---|
| Plate Pn | Shaft 15 kW | Load match |
| Input Pin | Pn/η≈16.7 | Billing |
| Efficiency η | 0.85~0.95 | Input=out/η |
| Plate In | Input A | Wire |
| Billing | On Pin | Not Pn |
Nameplate power is shaft output; input equals output over efficiency. Bill on input Pin not Pn or you undercount ~1/η. Size wire and breaker on plate In, the input current. Load matches Pn, distribution matches In.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machines per IEC 60034-1; rating per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.