A three-phase motor in star or delta has very different line and phase current. This page derives the relation for both connections so you can read the nameplate and size the cable.
In a star connection each winding sits between one line and the neutral, so the current through the winding, the phase current, is exactly the line current: I line equals I phase. Thus the cable is sized by line current and, when balanced, the three line currents are equal and 120 degrees apart with zero neutral current.
In a delta connection each winding spans two lines, so the line current is the vector difference of two winding currents and I line equals root three I phase. The same motor in delta has winding current only 1 over root three, about 58 percent, of the line current. The nameplate rated current for a delta motor is the line current, so size breakers, contactors and cable by that, not by the winding current.
| Conn | Line | Phase |
|---|---|---|
| Star Y | = phase | I line=I ph |
| Delta D | root3 x ph | I line=root3 I ph |
| Delta wind | line/root3 | 42 pct less |
| Cable | by line | nameplate |
| Neutral | Y bal 0 | unbal has |
| Start | star-delta | Y small |
The nameplate rated current is the line current; size every external device by it. Inside delta the winding current is smaller, but the line current is what sizes the cable. Star-delta starting exploits the smaller line current in star to soften start-up, so get the relation right or the protection is wrong.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rotating machines follow GB/T 755 and devices GB/T 14048. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.