Three phase power, rated current and power factor conversion shortcuts

How many amps does a 380 V motor draw per kilowatt, and how many kvar does a given load need? Memorize one conversion factor and the answer comes out on the spot. This page provides field ready shortcuts plus the exact formulas behind them.

1. How it works

The three phase relations are P equals the root of three times U times I times cos phi, Q equals P times tan phi, and S equals P over cos phi. On a 380 V system the product of the root of three and U is about 658, so I approximately equals P divided by 658 times cos phi. Check it: a 30 kW motor at cos phi 0.85 draws 30 over 658 times 0.85, about 53.6 A against a nameplate 56 A. At cos phi 0.85, tan phi is about 0.62, so the same motor pulls roughly 18.6 kvar of magnetizing power.

2. Practice and pitfalls

The field shortcut is 1.9 A per kW at cos phi 0.85, or roughly 2 A per kW when precision does not matter. Running the other way, P in kW is about 0.658 times I times cos phi. For compensation sizing, raising a 100 kW load from 0.75 to 0.95 requires P times the difference of tan phi values, 0.88 minus 0.33, which is 55 kvar. Remember that a 7 percent voltage sag pushes current up by about the same proportion, so convert ammeter readings to rated voltage before judging overload, and fall back to nameplate data and the full formula for formal design work.

3. Three phase conversion factor quick table

cosφA per kWtanφkvar per kW
0.752.000.880.88
0.801.900.750.75
0.851.790.620.62
0.901.690.480.48
0.951.600.330.33

4. Notes

Use the shortcut for patrol readings and compensation sizing; keep nameplate data and computed current for formal design. Convert readings to rated voltage before comparing.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power and energy definitions are covered by GB/T 12325, metering instruments by GB/T 17215, with low voltage distribution per GB 50054 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Applying the flat 2 A per kW rule to large loads at high power factor: error exceeds 10 percent, use the factor for the actual cos phi
② Ignoring voltage deviation when reading amps: a 7 percent sag raises current 7 percent and masks real overload
③ Back-calculating power from current while ignoring reactive share: apparent current is underestimated and cables run hot

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.