Active, reactive and apparent power in AC circuits

AC has three powers: real work, exchanged reactive and total apparent. This page explains active P, reactive Q and apparent S, and the right-triangle relation among them that underlies the power-factor charge on your bill.

1. How it works

Active power P equals U I cos phi in watts is the part that does real work, heat and mechanical output. Reactive power Q equals U I sin phi in var is shuttled back and forth by inductors and capacitors; it does no work but occupies the current path. Apparent power S equals U I in VA is the total capacity the source must supply, and S squared equals P squared plus Q squared.

2. Practice and pitfalls

Although reactive power makes no heat, it occupies transformer, cable and switch rating so S exceeds P and utilization drops. A 100 kVA transformer delivers 100 kW only at unity power factor; at 0.7 it gives just 70 kW and the rest of the capacity is eaten by Q. The utility bills demand on S and energy on P, and penalizes low power factor.

3. The three powers

PowerFormulaUnit
Active PUI cos phiW
Reactive QUI sin phivar
Apparent SUIVA
RelationS2=P2+Q2triangle
At 0.7P=0.7 SQ=0.714 S
Sizinguse Snot P

4. Notes

Separate P, Q and S when reading power. Size equipment and cable by S, bill and heating by P, and cut Q to raise cos phi is the way to save. Post the power triangle in the switchroom so newcomers see why the capacitor bank is not optional.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power quality follows GB/T 12325 and design GB/T 50052. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Sizing a transformer by P alone undersizes it and it trips on load
② Reading only S hides the real output and feels falsely adequate
③ Letting Q occupy capacity leaves the transformer underloaded and fined

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.