AC has three powers: real work, exchanged reactive and total apparent. This page explains active P, reactive Q and apparent S, and the right-triangle relation among them that underlies the power-factor charge on your bill.
Active power P equals U I cos phi in watts is the part that does real work, heat and mechanical output. Reactive power Q equals U I sin phi in var is shuttled back and forth by inductors and capacitors; it does no work but occupies the current path. Apparent power S equals U I in VA is the total capacity the source must supply, and S squared equals P squared plus Q squared.
Although reactive power makes no heat, it occupies transformer, cable and switch rating so S exceeds P and utilization drops. A 100 kVA transformer delivers 100 kW only at unity power factor; at 0.7 it gives just 70 kW and the rest of the capacity is eaten by Q. The utility bills demand on S and energy on P, and penalizes low power factor.
| Power | Formula | Unit |
|---|---|---|
| Active P | UI cos phi | W |
| Reactive Q | UI sin phi | var |
| Apparent S | UI | VA |
| Relation | S2=P2+Q2 | triangle |
| At 0.7 | P=0.7 S | Q=0.714 S |
| Sizing | use S | not P |
Separate P, Q and S when reading power. Size equipment and cable by S, bill and heating by P, and cut Q to raise cos phi is the way to save. Post the power triangle in the switchroom so newcomers see why the capacitor bank is not optional.