Which phase follows which decides motor direction. This page gives the standard way to check sequence with a phase rotation meter and a bulb-and-capacitor fallback when no meter is at hand.
Phase sequence is the order in which the three phases reach their peaks; positive ABC means A then B then C each 120 degrees later, reverse ACB is the opposite. Wrong sequence reverses a three-phase motor, breaks transfer logic and upsets some rectifiers, so always check after new wiring or switching.
A handheld phase meter has three leads to L1 L2 L3; powered, it shows forward or reverse. Match its voltage rating, say 100 to 500 V, keep leads insulated and hands off metal, and check the supply side before the motor so you do not read back-emf as source. Without a meter, a capacitor with two equal lamps in Y uses capacitive shift to reveal the order, but only as an emergency.
| Method | How | Judge |
|---|---|---|
| Meter | leads L1L2L3 | fwd green |
| Rating | match volts | 100-500 |
| Folk | cap + 2 lamps | bright/dim |
| When | new/switch | must check |
| Verify | vs nameplate | fan arrow |
| Safe | good insul | no touch |
Sequence is the last gate of wiring. After new install, switching or transfer, verify with a phase meter before energizing; a reversed motor means check sequence before mechanical jam. A phase meter is cheap and accurate, every bench should have one, never guess.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage devices follow GB/T 14048 and safety GB/T 16895. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.