The plate shows rise 80 K and class B; these must mesh or the winding overheats. This page pairs rise limit with insulation class.
Temperature rise limit ΔT is how much hotter the winding may be than the coolant (standard ambient 40℃), not absolute. Insulation class sets absolute limit: B 130℃, F 155℃, H 180℃. Allowed winding temp = 40℃ + rise. So B class with 80 K rise → 120℃ (10℃ margin); F with 105 K → 145℃ (10℃ margin). Rise and class must match; the gap is safety margin.
Why matched: if B class is marked 105 K rise, winding allowance 145℃ exceeds B 130℃, insulation ages fast (life halves per 8~10℃ over). Conversely F marked only 80 K is conservative derating, wasting capability. The two are a designed pair. Traps: reading class but not rise runs near the limit; hot ambient over 40℃ without derate exceeds absolute; an old motor over its rise still used ages insulation quickly.
In ambient above 40℃, derate about 1% per ℃, or check absolute: winding temp = ambient + measured rise must be below class limit. Example 50℃ ambient, B class 80 K rise → 130℃, at B limit with no margin, derate or move to F/H. Measure rise by IR or resistance: R2/R1=(235+T2)/(235+T1) for copper. Rule: ambient plus rise must stay under class limit, else derate or upgrade.
| Class | Limit | Rise | Margin |
|---|---|---|---|
| B | 130℃ | 80 K | 10℃ |
| F | 155℃ | 105 K | 10℃ |
| H | 180℃ | 125 K | 10℃ |
| Hot env | Derate | ~1%/℃ | Abs temp |
| Over rise | Ages | Load down | Upgrade |
Rise plus 40℃ ambient should equal class limit minus ~10℃ margin. B 80 K→120℃, F 105 K→145℃. Hot ambient derate ~1% per ℃, check absolute temp = ambient plus measured rise. Reading class but not rise runs near the limit.