Matching temperature rise limit with insulation class

The plate shows rise 80 K and class B; these must mesh or the winding overheats. This page pairs rise limit with insulation class.

1. How it works

Temperature rise limit ΔT is how much hotter the winding may be than the coolant (standard ambient 40℃), not absolute. Insulation class sets absolute limit: B 130℃, F 155℃, H 180℃. Allowed winding temp = 40℃ + rise. So B class with 80 K rise → 120℃ (10℃ margin); F with 105 K → 145℃ (10℃ margin). Rise and class must match; the gap is safety margin.

2. Numbers and practice

Why matched: if B class is marked 105 K rise, winding allowance 145℃ exceeds B 130℃, insulation ages fast (life halves per 8~10℃ over). Conversely F marked only 80 K is conservative derating, wasting capability. The two are a designed pair. Traps: reading class but not rise runs near the limit; hot ambient over 40℃ without derate exceeds absolute; an old motor over its rise still used ages insulation quickly.

3. Pitfalls and fixes

In ambient above 40℃, derate about 1% per ℃, or check absolute: winding temp = ambient + measured rise must be below class limit. Example 50℃ ambient, B class 80 K rise → 130℃, at B limit with no margin, derate or move to F/H. Measure rise by IR or resistance: R2/R1=(235+T2)/(235+T1) for copper. Rule: ambient plus rise must stay under class limit, else derate or upgrade.

4. Rise and class match

ClassLimitRiseMargin
B130℃80 K10℃
F155℃105 K10℃
H180℃125 K10℃
Hot envDerate~1%/℃Abs temp
Over riseAgesLoad downUpgrade

5. Notes

Rise plus 40℃ ambient should equal class limit minus ~10℃ margin. B 80 K→120℃, F 105 K→145℃. Hot ambient derate ~1% per ℃, check absolute temp = ambient plus measured rise. Reading class but not rise runs near the limit.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machines per IEC 60034-1; rating per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① B class marked 105 K rise exceeds limit and ages
② Hot ambient without derate exceeds absolute limit
③ Old motor over its rise still used ages fast

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.