Heating goes as I²R for both cable and fuse; coordination means the fuse clears before the cable overheats.
Rule: fuse rating ≤ cable ampacity; verify overload curve vs cable thermal limits and short-circuit breaking capacity.
Motor circuits use aM fuses for short-circuit only - overload needs a thermal relay.
| Cable | Ampacity | Fuse max | Note |
|---|---|---|---|
| 1.5mm² | 15~16A | 10~16A | Lighting |
| 2.5mm² | 20~25A | 16~20A | Sockets |
| 4mm² | 30~32A | 25~32A | Small power |
| 6mm² | 38~40A | 32~40A | Motors |
| 10mm² | 50~55A | 50A | Feeders |
| 16mm² | 65~70A | 63A | Large feeders |
Apply the points above to Fuse and cable coordination explained with Ohm's law; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 13539, IEC 60269, GB/T 14048.2, GB 50054 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.