Motor load torque measurement methods and tools

Before selection the worst is guessing load torque leaving either oversize or cannot move. This page explains how to measure load torque with dynamometer current method and torque wrench.

1. How it works

Most direct is a dynamometer magnetic powder eddy current or electric placed in the shaft reading steady torque N m and speed with high accuracy. A torque wrench fits low speed static such as a tightening shaft but cannot catch dynamic. Without a dynamometer hang a standard weight on a force arm at the load end and back solve T equals F times r force times arm.

2. Numbers and practice

Most convenient is the current method: measure phase current I at steady run and approximate torque T about k times I with k the torque constant from the sample for servo DC; for async use T about P divided by omega times eta. Prerequisite is the known efficiency curve. Example: large measured current and high temperature means load torque exceeds design. Under variable frequency use the torque current curve at that frequency not the power frequency value.

3. Pitfalls and fixes

Pit one: using no load current as load current undersizes the motor by half. Pit two: current method without dividing efficiency overestimates torque. Pit three: dynamometer range too small overload burns the sensor. Rule: use dynamometer or torque sensor for direct read when possible; otherwise current method divided by efficiency; catch peak load with a clamp meter at the start instant corresponding to near locked rotor torque.

4. Load torque measurement table

MethodToolAccuracyUse
Directdynamometerhighcalibration
Onlinetorque sensorhighmonitor
Infercurrent methodmediumfield quick
Statictorque wrenchlowlow speed
Noterange margindivide effcatch peak

5. Notes

Use dynamometer or torque sensor for direct read when possible; field quick measure uses current method inferring T about k I and divide by efficiency; catch peak load with a clamp meter at start instant. Keep range margin and never size from no load current.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor test see IEC 60034-2 and electrical safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① No load current as load current undersizes motor by half
② Current method without efficiency overestimates torque
③ Dynamometer range too small overload burns sensor

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.