A welded contact that will not open leaves the machine running when it should stop, sometimes with dangerous restart consequences. Welding almost always traces back to load selection or missing arc suppression. This page lists the four causes, how to confirm on site, and prevention.
Contact welding is contact-resistance heating plus arc melting fusing the contact faces together. Four typical causes: inductive loads strike a hot arc on opening and pull a metal bridge; lamp or capacitive loads draw a 10~15 times inrush on closing and spark-weld the faces; undersized contacts run hot under sustained overload; and tired springs or worn overtravel leave poor contact pressure that arcs. Since the arc strikes at opening, inductive loads are the number one culprit, so start by classifying the load.
On site: the coil lamp is out and the armature has dropped, yet the load still runs, or the open contact still beeps through. After isolating, lever the contacts apart and inspect: small beads may be dressed as a stopgap, but a broad molten face means the relay is scrapped. Then investigate the load, measure the inrush, check whether the suppression network died, and look for a stalled or shorted load. Replacing the relay without fixing the load only books a repeat visit within days.
| Cause | Mechanism | Field signature | Countermeasure |
|---|---|---|---|
| Inductive opening | Arc melts faces | Visible arc at opening | RC or free-wheel diode |
| Lamp inrush | 10~15x on closing | Spark at closing | Size at 10x derating |
| Overload heating | Contact resistance heat | Hot, discoloured terminals | Bigger relay |
| Pressure loss | Overtravel wear | Aged, poor contact | Replace at life end |
| Shorted load | Overcurrent melting | Broad molten face | Fix load first |
| Emergency | Lever apart, power off | Small beads may be dressed | Broad damage: replace |
Rule: before swapping the relay, investigate the load and the suppression network. Fit RC or free-wheel across inductive coils, derate lamp loads by ten, and replace hot contacts early. A dressed contact is a short-term measure only; log the load class and schedule a proper replacement with suppression.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contact performance per GB/T 14048.5; elementary relays per GB/T 21711.1; machinery safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.