Terminal voltage = EMF − I×r; open-circuit readings hide internal resistance.
DC method: r=(U0−U)/I with two load points; AC 1kHz meters give milliohm readings for batch checks.
Compare cells of the same type and state of charge; one high-resistance cell drags a whole series string.
| Battery | Healthy range | Method | Aging sign |
|---|---|---|---|
| Lead-acid 12V 100Ah | 3~8mΩ | AC meter | Doubled value |
| Li-ion 18650 | 20~50mΩ | AC meter | >80mΩ retire |
| CR2032 | 10~40Ω | DC drop | Drop widens |
| LiFePO4 100Ah | 0.2~0.5mΩ | AC meter | Spread between cells |
| Car starter | 3~6mΩ | DC high current | <9.6V cranking |
| UPS VRLA | 4~10mΩ | AC meter | Per-cell trend |
Test fully charged after 2h rest; track trends with one fixed method.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 31486 and product standards. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.