Main-circuit wiring and current-transformer hookup for thermal relays

Large motors exceed a thermal relay rating, so you step the current down with CTs to 5A before the relay. This page covers the direct and CT methods and how to scale the setting.

1. How it works

For small power, up to about 63A, the relay connects straight in the three-phase main circuit, its main contacts between supply and contactor, set directly to motor In. Torque the terminals about 2.0~2.5N·m, keep terminal rise under 60K, and wire the NC contact into the contactor coil circuit with the NO for alarm. All three bimetal elements must be in, because a missed phase loses that phase protection.

2. Practice and pitfalls

Above the relay maximum, typically 80~160A, use a 5A relay with three matching CTs stepping the primary down to 5A secondary. Pick the ratio by In/5: a 140A motor takes 150/5 or 200/5, giving 5A secondary, and the setting scales as In divided by ratio, so 140A with 200/5 (ratio 40) sets the relay at 3.5A. Never open the CT secondary, it makes dangerous voltage and burns the CT. Match polarity and ratio on all three phases, use shielded wire grounded at one point, and always rescale the setting when the ratio changes.

3. Main circuit and CT wiring table

CurrentMethodRelaySetting
Up to 63ADirect in lineBy motorSet to In
63-160ALarge frame80-160ASet to In
Above 160A5A relay + CTRatio In/5Scale secondary
140A example200/5 CT3.5A secondarySet 3.5A
CT wiringNo open secondaryPolarity matchP1/P2 correct
Ratio changeReset settingOr motor burnsLog it

4. Notes

Rule: small current direct, large current via 5A relay and CT with setting scaled to secondary not primary. Never open the CT secondary, match polarity, and always rescale on ratio change. Verify primary with a clamp and secondary with the dial before energising, and file both.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Relay and CT coordination per GB/T 14048.4, current transformers per GB/T 20840 series, safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Opening the CT secondary: dangerous induced voltage hurts people and burns the CT
② Ratio changed but setting not: protection basis wrong, motor burns on overload
③ CT polarity reversed: scaled current wrong phase, relay misjudges

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.