A PLC ladder rung is combinational logic drawn as contacts and coils. This page maps AND, OR and NOT gates onto normally open and normally closed contacts so relay thinking drops straight into ladder form.
In a PLC the input points are contacts and the logic result is a coil. AND is contacts in series: the coil energizes only when both conduct. OR is contacts in parallel: either one conducting is enough. NOT is a normally closed contact or an invert instruction. One rung reads left to right as signal flow, and the coil at the right end is the output, so a truth table can be translated into series and parallel contacts without drawing a single gate.
Worked example: interlock two motors. M1 may start when pushbutton SB1 is pressed and M2 is not running, so SB1 normally open in series with an M2 normally closed contact drives the M1 coil. The voter Y equals A and B, or A and C, or B and C becomes three parallel branches, each branch two series contacts. A ladder reads as who is in series with whom, which a veteran electrician understands at a glance.
Field traps: the PLC scans cyclically, so a combinational result updates only at the end of the scan, a few milliseconds at best. The worst trap is the double coil: the same coil appearing in two rungs, where the later one overwrites the earlier and the logic becomes erratic. Also think backwards about normally closed inputs, because their powered-off state is the opposite of what the drawing suggests.
| Logic | Ladder form | Watch out |
|---|---|---|
| AND | Contacts in series | All closed to conduct |
| OR | Contacts in parallel | One closed enough |
| NOT | Normally closed contact | State inverted |
| XOR | Series-parallel mix | Use an instruction |
| Latch | Self-holding contact | Not combinational |
| Double coil | Same coil, two rungs | Strictly forbidden |
Translate the truth table directly into series and parallel contacts; it is faster than drawing gates. Verify rung by rung with a PLC simulator or a force table, focusing on double coils and inversion direction.