One drive feeding several motors saves money, but one fault stops all. This page covers current, protection and sync differences to weigh.
One drive per motor gives independent control, precise per-motor over-current and overload protection, separate speed and start/stop, and a single fault stops only one motor. Cost is high with many drives and space. It fits lines where each motor needs its own speed, independent cycling and different process, like separate conveyor stations or auxiliary machines.
One drive for many uses a large VFD paralleling same-model same-power motors switched by contactors, all at one frequency and speed. It saves 30%~50% on drives and simplifies wiring, but total current adds up so the drive is sized on the sum, single-motor overload or phase loss is only caught by a thermal relay, and one motor fault can drag the bus; no individual speed. It suits synchronous multi-fan or pump groups.
Decide: many motors that must run in sync and simple process (cooling tower fans, exhaust groups) use one-drive-many to save; need independent speed, protection and fault isolation use one-per-motor. Traps: forgetting the simultaneity factor when summing current undersizes the drive; a seized motor in the group raises total current and thermal protection lags, burning it; mixing different powers unbalances current. Use one-drive-many only for synced groups.
| Item | One per motor | One for many |
|---|---|---|
| Cost | High | Low 30%~50% save |
| Protection | Per motor | Total only |
| Speed | Independent | Same speed |
| Fault | One stops | May hit group |
| Fit | Different stations | Sync fan groups |
Independent speed, protection and isolation need one-per-motor; synced same-speed simple groups use one-for-many to save. Sum current with simultaneity factor and margin; do not mix powers; rely on thermal relays per motor. Use one-for-many only for synced groups.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; distribution per GB/T 14048.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.