Trip classes and time-current behaviour of thermal relays

Class 10, Class 20 on the datasheet: what do they mean? Pick the wrong class for a long-starting motor and it either trips on every start or protects too slowly. This page defines the classes, explains the inverse-time curve and shows how to choose by starting time.

1. How it works

The trip class is the maximum trip time at 7.2 times the setting: Class 10A within 2~10 seconds, Class 10 within about 10 seconds, Class 20 within about 20, Class 30 within about 30. The class buys time for starting: fast light starts within seconds take Class 10; pumps and fans needing 10~20 seconds take Class 20; crushers and centrifuges starting in 20~30 seconds take Class 30; anything longer belongs on an electronic protector with stall detection, not on a bimetal relay.

2. Practice and pitfalls

The inverse-time curve shortens as the current multiple grows: no trip at 1.05 times, about 20 minutes at 1.2, 2~3 minutes at 1.5, under a minute at 2, and seconds at 7.2 according to class. The curve must sit below the motor thermal capability for protection yet above the starting current trace to ride through starts. On the datasheet graph, mark the 5~7 times starting current and the real starting time; the start point must fall left of the trip line with margin. If a machine trips at every start, check the class before blaming the hardware.

3. Trip class and application quick table

ClassTime at 7.2xStart time fitTypical duty
Class 10A2~10 sUnder 2 sFast light starts
Class 10Within 10 s2~8 sPumps, machine tools
Class 20Within 20 s8~15 sFans, centrifugal pumps
Class 30Within 30 s15~25 sCrushers, presses
Longer startsAbove 30 sOver 25 sElectronic protector
VFD circuitsCurve driftsNot applicableDrive electronic protection

4. Notes

Rule: pick the class from the worst-case starting time plus about 30% margin, nearer rather than farther; investigate the class before condemning the machine when starts trip; and hand VFD circuits to electronic protection. Mark the start point on the characteristic curve, sign only what you can see margin on.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Trip class definitions per GB/T 14048.4 (IEC 60947-4-1); overload coordination per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Class 10 on a long-starting load: every start trips the relay, endless fruitless repairs follow
② Choosing two classes high to stop nuisance trips: at real overload the relay waits too long and the motor accumulates heat damage
③ Keeping a bimetal relay in a VFD circuit: harmonic heating drifts the curve until the setting means nothing

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.