MY2N is the most common small interface relay on the shop floor: two changeover contacts on a plug-in socket. This page walks through the pin numbering, socket selection and polarity so you can wire it without guessing.
The MY2N carries two SPDT contacts rated AC250V/5A and DC30V/5A, and the coil voltage is given by the model suffix, for example MY2N-J AC220V or MY2N-J DC24V. On the original socket, pins 13 and 14 are the coil (same as A1/A2, positive to 13 for DC types), while the two changeover sets read 9-1-5 and 12-4-8: 9 and 12 are commons, 1 and 4 normally closed, 5 and 8 normally open. Compatible sockets such as HH52P use a different print: coil on 2 and 7, contacts on 1-3-4 and 8-6-5. Always trust the print on the socket you actually hold and verify with a continuity tester.
Fit a PYF08A type socket on a 35mm DIN rail, torque the screw terminals to about 0.5~0.9N·m and use 0.75~1.5mm² stranded wire with ferrules; bare strands under a screw loosen and heat up over time. Keep coil wiring and contact wiring separated, add a partition when 220V contact wiring shares the same socket area with signal lines, and pull the relay out only with power off. The keyed housing prevents reverse insertion, so if it resists, check the orientation instead of forcing it.
| Pin group | Function | Common print | Wiring note |
|---|---|---|---|
| Coil | Excitation | 13-14 (A1/A2) | DC: 13 positive, 14 negative |
| Contact set 1 | SPDT | 9-1-5 | 9 common, 1 NC, 5 NO |
| Contact set 2 | SPDT | 12-4-8 | 12 common, 4 NC, 8 NO |
| Compatible print | HH52P type | 2-7 coil | Contacts on 1-3-4 and 8-6-5 |
| Terminal torque | Screw fixing | 0.5~0.9N·m | Ferrules on 0.75~1.5mm² wire |
| Mounting | 35mm DIN rail | PYF08A | Clip home, insert with power off |
Rule: read the socket print before wiring, respect DC coil polarity, and never hot-swap a relay. Before first power-up, buzz out the coil and the natural contact states, then recheck after the coil is energised. When original and compatible relays share one cabinet, label the print differences so the next technician does not inherit the trap.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: General requirements for elementary electromechanical relays per GB/T 21711.1 (IEC 61810-1); electrical safety of machinery per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.