How to tell a normally-open from normally-closed contact

NO and NC are the most basic relay and contactor idea, yet beginners swap them and wire self-hold or interlock wrong. Here is how to judge with a meter, symbol and number.

1. How it works

Normally Open (NO) means the contact is open with the coil de-energised (released) and closes after pull-in. Normally Closed (NC) is closed when released and opens after pull-in. The reference state is always the coil-de-energised natural state, not after pull-in. Many people measure while the contactor is held in and read everything backwards; this one rule avoids half the mistakes.

2. Numbers and practice

The reliable way: de-energise, set the meter to continuity, touch the two contact ends. A beep means NC (conducts), silence means NO (open). Then press the armature by hand to mimic pull-in: what beeped goes silent (NC opens), what was silent beeps (NO closes), confirming it. By number, 13-14 is usually NO and 21-22 usually NC, but makers differ, so trust the meter.

3. Pitfalls and fixes

Pit one: memorising symbols without measuring, then a non-standard or old model number mismatches and you wire it reversed. Pit two: uneven hand pressure gives intermittent contact and a wrong reading. Pit three: measuring live, the coil jitters, state changes and you risk a short. De-energise, use the buzzer, read the natural state then press to confirm, treat numbers as a hint only.

4. NO vs NC judgement quick table

ItemCoil de-energisedPulled in
NOOpen (silent)Closed (beep)
NCClosed (beep)Open (silent)
Number13-14 usually NO21-22 usually NC
MeasureBuzzer no tonePress, tone
ReferenceUse de-energisedDo not judge held
NoteNumbers differTrust the meter

5. Notes

Rule: judge by the de-energised natural state, buzzer beep is NC, silence is NO; press to flip and confirm. Numbers are a hint only, non-standard types go by measurement, never test live.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control circuit and contact definitions per GB/T 14048.5, contactor product per GB/T 14048.4. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Symbols only, no measure: non-standard old type mismatches, wired reversed
② Uneven hand pressure: intermittent contact, wrong state read
③ Measuring live: coil jitters, state changes, risk of short

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.