NO and NC are the most basic relay and contactor idea, yet beginners swap them and wire self-hold or interlock wrong. Here is how to judge with a meter, symbol and number.
Normally Open (NO) means the contact is open with the coil de-energised (released) and closes after pull-in. Normally Closed (NC) is closed when released and opens after pull-in. The reference state is always the coil-de-energised natural state, not after pull-in. Many people measure while the contactor is held in and read everything backwards; this one rule avoids half the mistakes.
The reliable way: de-energise, set the meter to continuity, touch the two contact ends. A beep means NC (conducts), silence means NO (open). Then press the armature by hand to mimic pull-in: what beeped goes silent (NC opens), what was silent beeps (NO closes), confirming it. By number, 13-14 is usually NO and 21-22 usually NC, but makers differ, so trust the meter.
Pit one: memorising symbols without measuring, then a non-standard or old model number mismatches and you wire it reversed. Pit two: uneven hand pressure gives intermittent contact and a wrong reading. Pit three: measuring live, the coil jitters, state changes and you risk a short. De-energise, use the buzzer, read the natural state then press to confirm, treat numbers as a hint only.
| Item | Coil de-energised | Pulled in |
|---|---|---|
| NO | Open (silent) | Closed (beep) |
| NC | Closed (beep) | Open (silent) |
| Number | 13-14 usually NO | 21-22 usually NC |
| Measure | Buzzer no tone | Press, tone |
| Reference | Use de-energised | Do not judge held |
| Note | Numbers differ | Trust the meter |
Rule: judge by the de-energised natural state, buzzer beep is NC, silence is NO; press to flip and confirm. Numbers are a hint only, non-standard types go by measurement, never test live.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control circuit and contact definitions per GB/T 14048.5, contactor product per GB/T 14048.4. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.