How the field winding is connected decides the speed characteristic and the application of a DC machine. One comparison table plus a field identification method settle most selection questions.
Separately excited machines feed the field from an independent source and offer the most flexible speed control. Shunt motors parallel the field with the armature: many turns of fine wire drawing one to five percent of rated current, a stiff characteristic dropping only three to eight percent from no load to full load. Series machines carry the full armature current through a few turns of heavy wire, so flux grows with current and torque rises roughly with the square of current, ideal for traction, hoisting and forklifts. Compound machines combine both windings to trade between starting torque and speed stability.
The dangerous case is loss of field on a shunt or compound machine at light load: back-EMF collapses, armature current soars and the speed runs away, which is why field-failure protection in the excitation circuit is mandatory, not optional. Series motors must never run unloaded or on belt drive; direct coupling or gearing is required, since the no-load speed is limited only by friction. In the field, identify the type by resistance: shunt field reads hundreds to thousands of ohms, armature a fraction of an ohm to a few ohms, series field the smallest value of all.
| Excitation | Speed characteristic | Starting torque | Typical application |
|---|---|---|---|
| separately excited | independently controllable, stiff | medium | precision drives, servo |
| shunt | stiff, 3~8% droop at full load | medium | machine tools, fans, pumps |
| series | soft, races unloaded | huge (proportional to I²) | traction, hoisting, forklift |
| accumulative compound | fairly stiff with load compensation | large (over 50% above shunt) | rolling mills, elevators |
| differential compound | rises with load | small | rare, test rigs |
| permanent magnet | like separately excited, no field supply | medium | small servo, automotive |
Field-failure protection belongs on every shunt or compound machine: a current relay in the excitation circuit trips the armature supply below setpoint. After overhaul, confirm the original coupling method before returning a series motor to service.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 755 (IEC 60034-1) for ratings and performance of rotating machines; DC machine test methods per GB/T 1311. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.