An intermediate relay and a contactor look alike, but the relay handles signals and small loads, with small capacity and many poles. Here are the differences and where each fits.
An intermediate relay has small contacts, typically 5~10A/250VAC, used to amplify and switch control signals, expand contact count and isolate strong and weak circuits; it does not drive a big motor. A contactor has large contacts (9A to hundreds of A) switching the motor feeder directly. In short: the relay manages logic, the contactor manages power. Coils are similar but contacts and arc control differ hugely.
The relay packs several poles (2~4 changeover), small with many circuits, good for PLC output expansion, lamps, alarms, small solenoids. A contactor is usually 3 main plus some aux, main contacts with arc chute for big-current arcs. The relay has almost no arc control; on a big load it welds and burns. Never use a relay in a power feeder instead of a contactor.
Pit one: in a pinch driving a motor (other than a contactor coil) from a relay, contacts weld. Pit two: wiring a relay into the main circuit, no arc control burns the case. Pit three: PLC output driving a big load directly without buffering, burns the output point. Use the relay for signals and small loads, the contactor for power, buffer PLC outputs through a relay.
| Item | Inter. relay | Contactor |
|---|---|---|
| Contact | 5~10A | 9A~hundreds |
| Use | Signal/small | Power switch |
| Poles | 2~4 change | 3 main+aux |
| Arc | Almost none | Arc chute |
| Motor | No | Yes |
| Role | Logic isol. | Main loop |
Rule: intermediate relay small contacts (5~10A), many poles, handles signals, small loads, contact expansion, strong-weak isolation; contactor big contacts with arc chute handles power. Never put a relay in the main feeder instead of a contactor.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage control per GB/T 14048.5, contactor per GB/T 14048.4, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.