The plate says 1460 vs sync 1500; that 40 rpm is slip, hiding load and health. This page computes slip and shows how it reflects load.
Synchronous speed ns = 60f/p (f=50 Hz, p pole pairs). 4-pole p=2 gives ns=1500 r/min; 6-pole p=3 gives 1000. Actual rotor n is slightly below ns, slip Δn=ns-n, slip rate s=(ns-n)/ns. A 4-pole 1460 plate: s=(1500-1460)/1500≈2.67%. Slip grows with load: near 0 no-load, 2%~5% full-load, 1 (100%) at stall.
Example reverse from plate: n=970, f=50, ns just above 970 is 1000, so p=60×50/1000=3, a 6-pole; s=3%. n=730 gives ns=750, p=4, 8-pole, s=2.67%. Use: check plate poles match the frame; under VFD overspeed ns changes with f and so does s.
Same load with larger slip means the motor strains: low voltage, aged windings or tight bearing raise s and drop n. If measured n falls well below plate (s from 3% to 8%), check under-voltage or mechanical jam; stall s=1 draws max current. Traps: picking wrong ns when reversing poles (1460 misread as 1440); using fixed 50 Hz ns under VFD gives wrong s, use actual f. Compare measured speed to plate for quick health check.
| Poles | Sync | Plate | Slip |
|---|---|---|---|
| 4 | 1500 | 1460 | 2.67% |
| 6 | 1000 | 970 | 3.00% |
| 8 | 750 | 730 | 2.67% |
| 2 | 3000 | 2930 | 2.33% |
| Stall | ns | 0 | 100% |
Sync ns=60f/p, slip s=(ns-n)/ns, about 2%~5% full load. Reverse poles from plate by taking the next standard ns above. Rising slip means strain (under-voltage, aging, tight bearing). Under VFD use actual f for s, not fixed 50 Hz. Compare measured speed to plate for health.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machines per IEC 60034-1; rating per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.