Calculating nameplate speed and slip rate with examples

The plate says 1460 vs sync 1500; that 40 rpm is slip, hiding load and health. This page computes slip and shows how it reflects load.

1. How it works

Synchronous speed ns = 60f/p (f=50 Hz, p pole pairs). 4-pole p=2 gives ns=1500 r/min; 6-pole p=3 gives 1000. Actual rotor n is slightly below ns, slip Δn=ns-n, slip rate s=(ns-n)/ns. A 4-pole 1460 plate: s=(1500-1460)/1500≈2.67%. Slip grows with load: near 0 no-load, 2%~5% full-load, 1 (100%) at stall.

2. Numbers and practice

Example reverse from plate: n=970, f=50, ns just above 970 is 1000, so p=60×50/1000=3, a 6-pole; s=3%. n=730 gives ns=750, p=4, 8-pole, s=2.67%. Use: check plate poles match the frame; under VFD overspeed ns changes with f and so does s.

3. Pitfalls and fixes

Same load with larger slip means the motor strains: low voltage, aged windings or tight bearing raise s and drop n. If measured n falls well below plate (s from 3% to 8%), check under-voltage or mechanical jam; stall s=1 draws max current. Traps: picking wrong ns when reversing poles (1460 misread as 1440); using fixed 50 Hz ns under VFD gives wrong s, use actual f. Compare measured speed to plate for quick health check.

4. Speed slip examples

PolesSyncPlateSlip
4150014602.67%
610009703.00%
87507302.67%
2300029302.33%
Stallns0100%

5. Notes

Sync ns=60f/p, slip s=(ns-n)/ns, about 2%~5% full load. Reverse poles from plate by taking the next standard ns above. Rising slip means strain (under-voltage, aging, tight bearing). Under VFD use actual f for s, not fixed 50 Hz. Compare measured speed to plate for health.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machines per IEC 60034-1; rating per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Wrong ns when reversing poles miscomputes pole count
② Using 50 Hz ns under VFD gives wrong slip
③ Measured speed far below plate means under-voltage or jam

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL