A contactor coil draws several times more at pick-up than at hold; this sets the control supply size and the need for an economiser. Miss it and the supply sags or the DC coil burns.
An AC coil is inductive; with the armature released the air gap is largest, reluctance high, reactance low, current high. After pull-in the gap vanishes, reactance rises and current drops sharply. Pick-up current is about 6~10 times the hold current, hold power only 10%~20% of pick-up. A DC coil is resistive with near-equal pick-up and hold current, so it needs a series economy resistor to cut hold current or it runs hot forever.
Size the control supply to the pick-up total, because the start surge of many contactors together far exceeds the hold load. A 220V coil at 60VA pick-up and 8VA hold means ten together need about 600VA instant but only 80VA holding. The transformer must ride the surge with margin or voltage sags and some fail to seat. A DC coil gets the economy resistor after pick-up, dropping current to about 1/3~1/2.
Pit one: sizing the transformer to hold current, the collective pick-up sags voltage and some chatter. Pit two: a broken or missing DC economiser keeps full current after pull-in, coil smokes in minutes. Pit three: a thyristor DC hold with no saving runs the coil hot. Size supply to the pick-up surge, always fit the DC economiser and measure hold current.
| Item | Pick-up | Hold |
|---|---|---|
| AC coil | 6~10x current | Drops to 10%~20% |
| DC coil | Needs economiser | Resistor to 1/3~1/2 |
| Power eg | 60VA pick-up | 8VA hold |
| Supply size | By pick-up surge | With margin |
| Ten together | 600VA instant | 80VA hold |
| Wrong result | Sag, chatter | No resistor, burn |
Rule: AC draws big at pick-up small at hold, size supply to the surge; DC coil current is steady so fit an economiser to about one third. Measure hold current, never let the coil run at full current.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor standard per GB/T 14048.4, control circuit per GB/T 14048.5, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.