A synchronous motor cannot simply be switched on and run; starting needs care. This page covers the common asynchronous start using the damper winding, the pull-in process, and alternatives like VFD starting.
A synchronous rotor is a fixed magnetic pole, so at standstill the stator field sweeps past with zero average torque and no self-start. It must be brought near synchronous speed first, then excited. The usual method embeds a damper cage on the pole faces; with no excitation the stator drives the rotor like an induction motor up to 95 to 98 percent speed, then DC excitation is applied and magnetic pull drags it into step. The damper also damps oscillation later.
Other starts: a VFD ramps frequency from zero for shock-free synchronous acceleration, best for large or frequent starts but costly; a pony motor drags it to speed; or a variable-frequency supply. In asynchronous start the field winding must be closed through a resistor or shorted during acceleration to avoid induced high voltage that ruins insulation, never left open. Keep starting current within limits and only apply excitation near synchronous speed.
| Method | Principle | Merit | Where used |
|---|---|---|---|
| Asynchronous start | Damper winding | Simple, common | General |
| VFD start | Ramp from 0 Hz | No shock | Large power |
| Pony motor | Small driver | Smooth | Special cases |
| Field with resistor | Blocks overvoltage | Protects insulation | Always do it |
| Pull-in | Apply excitation | Into step | The key step |
A synchronous motor cannot start itself: bring it near synchronous speed first, then excite. The usual route is asynchronous starting, where the damper winding acts like a squirrel cage and accelerates the rotor to 95%~98% of synchronous speed before DC excitation pulls it into step. The rule that saves the insulation: during starting the field winding must be closed through a resistor or shorted, never left open, or it generates a destructive high voltage. Large machines prefer VFD starting.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Synchronous machines: GB/T 755 / IEC 60034-1; drives: GB/T 12668 / IEC 61800. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.