Starting methods of synchronous motors and asynchronous start

A synchronous motor cannot simply be switched on and run; starting needs care. This page covers the common asynchronous start using the damper winding, the pull-in process, and alternatives like VFD starting.

1. How it works

A synchronous rotor is a fixed magnetic pole, so at standstill the stator field sweeps past with zero average torque and no self-start. It must be brought near synchronous speed first, then excited. The usual method embeds a damper cage on the pole faces; with no excitation the stator drives the rotor like an induction motor up to 95 to 98 percent speed, then DC excitation is applied and magnetic pull drags it into step. The damper also damps oscillation later.

2. Practice and pitfalls

Other starts: a VFD ramps frequency from zero for shock-free synchronous acceleration, best for large or frequent starts but costly; a pony motor drags it to speed; or a variable-frequency supply. In asynchronous start the field winding must be closed through a resistor or shorted during acceleration to avoid induced high voltage that ruins insulation, never left open. Keep starting current within limits and only apply excitation near synchronous speed.

3. Starting methods and asynchronous starting of synchronous motors

MethodPrincipleMeritWhere used
Asynchronous startDamper windingSimple, commonGeneral
VFD startRamp from 0 HzNo shockLarge power
Pony motorSmall driverSmoothSpecial cases
Field with resistorBlocks overvoltageProtects insulationAlways do it
Pull-inApply excitationInto stepThe key step

4. Notes

A synchronous motor cannot start itself: bring it near synchronous speed first, then excite. The usual route is asynchronous starting, where the damper winding acts like a squirrel cage and accelerates the rotor to 95%~98% of synchronous speed before DC excitation pulls it into step. The rule that saves the insulation: during starting the field winding must be closed through a resistor or shorted, never left open, or it generates a destructive high voltage. Large machines prefer VFD starting.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Synchronous machines: GB/T 755 / IEC 60034-1; drives: GB/T 12668 / IEC 61800. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Leaving the field winding open during start induces a high voltage that punctures the insulation
② Applying excitation below synchronous speed fails to pull in and the machine falls out of step
③ Closing the breaker DOL gives the rotor no torque, leaving vibration, noise and a cooked stator

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.