Picking a VFD by nameplate kW alone fails on heavy or long-cable duty. This page gives a step-by-step current, overload and cable calculation.
VFD nameplate power is sized on a 4-pole motor, but you size by the motor rated current Ie. The drive rated output current must exceed Ie times service factor. A 6/8-pole low-speed motor draws more current at the same kW, so upsize a step. Example: 22 kW 4-pole Ie≈42 A needs a 45 A drive; 22 kW 6-pole Ie≈48 A needs the 55 A class. Rule one: size by amperes, not kW.
Fan/pump squared-torque loads use light-overload drives (110% 60 s) cheaply; constant-torque, hoist and press use heavy-overload (150% 60 s). If start torque is 1.5× rated the drive overload must cover it, and injection or press peaks of 2~3× need a step up or permitted duty cycle. Trap: a light-overload drive on constant torque trips on frequent start.
Beyond 50 m cable, account for drop and capacitance; upsize the wire or add an output reactor or waveform distorts and the motor heats. Drop ΔU≈√3·I·L·R should stay under 2% rated. At over 40℃ derate about 1% per ℃, and 10%~20% in a sealed cabinet. Keep 10%~15% current margin for aging. Rule: current first, heavy-duty step up, long cable thicker, high temp derate.
| Step | Point | Criterion |
|---|---|---|
| 1 current | Inv≥Ie×factor | Amps not kW |
| 2 overload | Light for sq torque | Heavy for const |
| 3 cable | Drop<2% thicker | Long add reactor |
| 4 ambient | High temp derate | ~1%/℃ |
| 5 margin | Keep 10%~15% | Aging |
Size by motor rated current not power; drive current must exceed nameplate. Constant torque and hoists need heavy overload. Long cable over 2% drop needs thicker wire or reactor; derate about 1% per ℃ above 40. Keep 10%~15% margin.