How to size a VFD to match the motor: calculation steps

Picking a VFD by nameplate kW alone fails on heavy or long-cable duty. This page gives a step-by-step current, overload and cable calculation.

1. How it works

VFD nameplate power is sized on a 4-pole motor, but you size by the motor rated current Ie. The drive rated output current must exceed Ie times service factor. A 6/8-pole low-speed motor draws more current at the same kW, so upsize a step. Example: 22 kW 4-pole Ie≈42 A needs a 45 A drive; 22 kW 6-pole Ie≈48 A needs the 55 A class. Rule one: size by amperes, not kW.

2. Numbers and practice

Fan/pump squared-torque loads use light-overload drives (110% 60 s) cheaply; constant-torque, hoist and press use heavy-overload (150% 60 s). If start torque is 1.5× rated the drive overload must cover it, and injection or press peaks of 2~3× need a step up or permitted duty cycle. Trap: a light-overload drive on constant torque trips on frequent start.

3. Pitfalls and fixes

Beyond 50 m cable, account for drop and capacitance; upsize the wire or add an output reactor or waveform distorts and the motor heats. Drop ΔU≈√3·I·L·R should stay under 2% rated. At over 40℃ derate about 1% per ℃, and 10%~20% in a sealed cabinet. Keep 10%~15% current margin for aging. Rule: current first, heavy-duty step up, long cable thicker, high temp derate.

4. VFD sizing steps

StepPointCriterion
1 currentInv≥Ie×factorAmps not kW
2 overloadLight for sq torqueHeavy for const
3 cableDrop<2% thickerLong add reactor
4 ambientHigh temp derate~1%/℃
5 marginKeep 10%~15%Aging

5. Notes

Size by motor rated current not power; drive current must exceed nameplate. Constant torque and hoists need heavy overload. Long cable over 2% drop needs thicker wire or reactor; derate about 1% per ℃ above 40. Keep 10%~15% margin.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; machines per IEC 60034-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Sizing by kW undersizes low-speed high-current motors
② Light-overload drive on constant torque trips; use heavy
③ Long cable without derate distorts waveform and heats motor

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.