Temperature coefficient of resistance: why motor winding resistance differs cold vs hot

Copper resistance rises linearly with temperature; cold and hot winding readings differ over ten percent.

1. How it works

R2=R1×(234.5+t2)/(234.5+t1) for copper (225 for aluminium); α≈0.00393/℃ near room temperature.

2. Practice and pitfalls

Resistance-method temperature rise: +4% resistance ≈ +10K. Convert cold readings to the reference temperature before comparing with design values.

3. Winding resistance vs temperature

Winding tempCu relative RTypical caseNote
10℃0.961Winter factory testAl uses 225
20℃1.000ReferenceCommon base
40℃1.078Hot shop floor+7.8%
75℃1.216Class A baseOld standard
95℃1.295Class B baseHeat-run point
115℃1.418Class F baseVFD motors
135℃1.512Class H baseCrane motors
155℃1.706Limit hotspotLife collapses

4. Notes

Record winding temperature right after the resistance reading; aluminium and copper constants must not be mixed.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 1032 and GB 755 for rotating machines. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Comparing cold readings with hot design values
② Skipping the temperature record
③ Using 234.5 for aluminium windings

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.