Copper resistance rises linearly with temperature; cold and hot winding readings differ over ten percent.
R2=R1×(234.5+t2)/(234.5+t1) for copper (225 for aluminium); α≈0.00393/℃ near room temperature.
Resistance-method temperature rise: +4% resistance ≈ +10K. Convert cold readings to the reference temperature before comparing with design values.
| Winding temp | Cu relative R | Typical case | Note |
|---|---|---|---|
| 10℃ | 0.961 | Winter factory test | Al uses 225 |
| 20℃ | 1.000 | Reference | Common base |
| 40℃ | 1.078 | Hot shop floor | +7.8% |
| 75℃ | 1.216 | Class A base | Old standard |
| 95℃ | 1.295 | Class B base | Heat-run point |
| 115℃ | 1.418 | Class F base | VFD motors |
| 135℃ | 1.512 | Class H base | Crane motors |
| 155℃ | 1.706 | Limit hotspot | Life collapses |
Record winding temperature right after the resistance reading; aluminium and copper constants must not be mixed.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 1032 and GB 755 for rotating machines. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.