Loss of synchronism in synchronous motors: causes

When a synchronous motor loses step it trips, and the root is the load angle crossing its limit. This page describes the symptoms, what pushes it out of the stable region, and how to prevent it.

1. How it works

At loss of synchronism the rotor slips past the stator field; stator current swings wildly, active power flickers positive and negative, and the unit groans with low-frequency vibration until protection trips. If it loses step under load, the load is thrown off and speed may overshoot or stall. Wild current swing plus trip points to loss of step rather than a short circuit.

2. Practice and pitfalls

The root is load angle exceeding the 90-degree static limit, triggered by sudden mechanical overload, a system voltage dip that collapses maximum power, loss of excitation that zeroes E, a large disturbance such as a fault or shock load, or frequency jump. All let the magnetic pull fail to hold the rotor. Prevention keeps a margin below the limit, fits loss-of-field and over-load protection, supports voltage, and monitors power factor and active power; on seeing swing, reduce load or raise excitation. VFD-driven synchronous machines limit angle by controller and rarely lose step but still must avoid commanded overload.

3. Out-of-step causes and signatures of synchronous machines

CauseMechanismSignCountermeasure
OverloadDelta past limitSwinging currentShed load
Voltage dipPmax dropsOscillationSupport voltage
Loss of fieldE collapsesNegative varsCheck excitation
Short circuitDisturbanceImpactProtection
Frequency changeOut of syncAbnormal noiseStabilise freq

4. Notes

Loss of synchronism shows up as violent stator current swings, active power flipping sign, a low-frequency growl and a trip; the root cause is delta passing 90 degrees. Overload, sudden voltage dips, loss of field, short-circuit disturbances and frequency steps can all trigger it. Prevention: keep angle margin, fit loss-of-field and overload protection, watch the power factor, and shed load or boost excitation the moment the current starts swinging.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Synchronous machines: GB/T 755 / IEC 60034-1; relay protection: GB/T 14285. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Chasing a short circuit when the current is merely swinging misreads loss of synchronism
② Ignoring loss of field lets E collapse and the power collapses with it
③ Living close to the delta limit means any small disturbance trips the machine

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.