CTs isolate magnetically and suit AC 5A to kiloamps; shunts are milliohm resistors with live terminals.
Shunts win on DC accuracy (0.1%) but need isolation electronics; CT secondaries must never run open-circuit.
For VFD output use wideband Hall or Rogowski coils; iron CTs saturate with DC components.
| Aspect | Current transformer | Shunt |
|---|---|---|
| Principle | Magnetic induction | Resistive drop |
| Isolation | Yes | None - live |
| Range | AC 5A~kA | DC/AC, ≤ hundreds A |
| Frequency | Power frequency | DC~100kHz |
| Accuracy | 0.2~1 class | 0.1~0.5% |
| Fatal risk | Open-secondary HV | Loose joints heat |
| Output | 5A/1A or mV | 75mV standard |
Apply the points above to Current transformer vs shunt for current measurement; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB 20840.1, GB 1208, GB/T 7676.9 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.