Excess vibration cracks foundations, breaks couplings and wreck bearings fast. This page separates mechanical from electromagnetic vibration sources, gives the numeric limits and a location procedure so the shake has somewhere to start.
Judge vibration by velocity RMS in mm/s. The standard sets about 2.8 as good for small machines, 2.8 to 4.5 usable but watched, over 4.5 unacceptable, over 7.1 severe. Sources split mechanical (rotor imbalance, misalignment, loose foundation, bad coupling, failed bearing) and electromagnetic (uneven air gap, winding fault, supply harmonics). Mechanical vibration grows with speed and tracks load; electromagnetic is high frequency tied to voltage or current anomaly and often vanishes the instant power is cut.
Mechanical sources dominate: poor rotor balance shows a strong one times speed frequency from a single keyway, biased fan or loose end windings; misalignment shows two times speed plus axial vibration; loose feet show low frequency sway; bad bearing shows its defect frequency; unbalanced pulley adds its own. Fix by rebalancing, laser aligning within 0.05 mm, tightening and grouting, or changing the bearing. Electromagnetic causes: uneven air gap from fit eccentricity or bearing wear gives two times line frequency; turn short or broken bar gives current ripple and specific frequencies; drive harmonics give high frequency hum above a few hundred Hz. Locate by running uncoupled off load, checking current balance and air gap with a feeler at four points within 5 to 10 percent, and log the trend for early action.
| Source | Signature frequency | Fix |
|---|---|---|
| rotor imbalance | 1x speed | rebalance |
| misalignment | 2x speed plus axial | laser align |
| loose feet | low freq sway | tighten grout |
| bad bearing | bearing defect freq | change bearing |
| uneven gap | 2x line freq | align change bearing |
| em or harmonic | high freq hundreds Hz | check winding filter |
Judge by velocity RMS, good at 2.8, fail over 4.5 and severe over 7.1. Run uncoupled to split mechanical from electromagnetic, then check current balance and air gap within 5 to 10 percent. Mechanical faults yield to balancing, laser alignment under 0.05 mm, tightening and bearing change; log the trend for early intervention.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Mechanical vibration per GB/T 10068; rating per GB/T 755 (IEC 60034-1). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.