Relay contact rating and how much load it can really switch

A relay rated 5A/10A only reaches that figure on resistive load; inductive, lamp and DC loads need big de-rating.

1. How it works

The marked capacity, e.g. 5A/250VAC or 10A/28VDC, is the safe current under resistive load such as resistors, indicator lamps and solenoid coils. On inductive load (relay or contactor coils, small motors) the break arc energy is high, so the real allowed current drops to about 0.3~0.5 of rating. An incandescent lamp draws 10~15 times cold inrush, also needing heavy de-rating or a surge-rated type.

2. Practice and pitfalls

Resistive (heating, LED indicator) can run full 5A. Inductive (coils, small motors) falls to 1~2A or uses an RC snubber. Lamp load runs at 0.1~0.2 of rating or a surge type. Capacitive (capacitor-input supply) has large inrush and must de-rate. DC is harder to clear than AC, so same-size DC allowed current is about 1/3~1/2 of AC. Pick by the real load class against the maker curve.

3. Relay load de-rating quick table

Load typeFactorNote
Resistive1.0 (full 5A)Resistor/indicator
Inductive0.3~0.5Coils/small motor
Lamp0.1~0.2Cold inrush big
CapacitiveDe-rateLarge inrush
DC1/3~1/2 of ACHard to clear
MeasureRC on inductiveLonger life

4. Notes

Rule: the 5A nameplate is full only on resistive; inductive to 0.3~0.5, lamp 0.1~0.2, DC times 1/3. De-rate hard on coil groups and lamps, add RC on inductive loads for life.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage control per GB/T 14048.5, relay product per its standard, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Running coil groups at full 5A: break arc accumulates, contacts age early
② DC load using AC rating: poor arc clear, welds
③ No de-rating on lamp: 10~15x cold inrush wrecks contacts

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.