Entering nameplate data into the VFD parameters

After fitting a VFD you load plate data; wrong entry means trips or overheating. This page lists mandatory parameters and how to auto-tune.

1. How it works

The VFD motor parameter group must receive: rated power Pn, voltage Un, current In, frequency Fn (50 Hz), speed n, poles/sync speed. Most critical are In and n, used for vector control and slip compensation. Omitting or mistyping In biases overload protection and torque calculation, either tripping falsely or failing to protect a real overload. Voltage follows the Δ/Y connection on the plate.

2. Numbers and practice

Advanced drives offer motor auto-tuning (static or rotating): after entry the drive measures stator resistance, leakage inductance and rotor time constant, writes them to the model and sharply improves vector accuracy. Steps: enter basics → set tuning command → free the shaft (rotating tune needs load disconnected) → execute → save. Trap: rotating tune with load attached or no zero-speed set makes the motor spin suddenly and hurt; static tune is safest though slightly less precise.

3. Pitfalls and fixes

After entry, monitor: no-load current should be ≈0.2~0.5 In and overload default 100%~150% sensible. If it reports overload while truly unloaded, In is wrong or tuning skipped. For one-drive-many, enter each motor separately. Rule: enter In/n/Fn first, auto-tune, then verify on monitor. If the plate is lost, use measured values from the prior page.

4. VFD entry parameters

ParameterSourceEffect
PnPlateBase
UnPlate connectOutput
InPlateProtect/torque
Fn50 HzSync
nPlateSlip comp
TuneAutoVector

5. Notes

Enter In, n, Fn, Un, Pn; In and n drive protection and torque. Do motor auto-tune (static safest) for vector accuracy. After entry monitor no-load current ≈0.2~0.5 In. Missing In causes false or missed overload trips.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; machines per IEC 60034-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Missing/wrong In mis-trips or fails to protect overload
② Rotating tune with load attached spins and hurts
③ Skipping auto-tune gives poor vector and false overload

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.